Siemens Building Technologies Product-Data Sheet Radio signal unit REV... CE1N2255en
Landis & Staefa Division 16.10..2000
If the displayed room temperature does not agree with the measured room tempera-
ture, the temperature sensor can be recalibrated.
When the setting slider is set to position
Day /
, press button . Then, the display will
change as follows:
1234567
0 6 12 18 24
2252Z14
By pressing button or , the temperature can be changed in increments of 0.2
°C (max. ±2 °C). On completion of the readjustment, the setting slider must be reset to
the Auto / Run position.
When pressing buttons
and simultaneously, all individual settings will
be reset to their standard values.
Resetting also serves as a display check:
1234567
0 6 12 18 24
COOLING
2252Z13
After a reset, all individual settings such as time of day, weekday, switching times, etc.,
must be re-entered.
Technical design of controller / transmitter REV22RF
OPTIMUM P.1
OFF
1h / °C
1/2h / °C
1/4h / °C
123
2252Z01
P.1
Optimization brings forward the switch-on point P.1 such that the adjusted setpoint will
be reached at the desired time. The setting depends on the type of control system in
use, that is, on heat transmission (piping system, radiators), building dynamics (building
mass, insulation), and heating output (boiler capacity, flow temperature). The optimiza-
tion is set with DIP switch no.1 as follows:
OFF No effect
1/4h/°C For fast controlled systems
1/2h/°C For medium controlled systems
1h/°C For slow controlled systems
t
T
17
18
19
- 4
- 2
2252D01
16
- 3
1/4h/°C
1/2h/°C
1h/°C
P.1
- 2
- 1
- ½
- 1½
- 1
- ½
- ¼- ¾
P
on
20
°C
T1
- 1
h
h
h
TR
x
h
h
h
h
h
h
h
h
h
T Temperature (°C) TR
x
Actual value of room temperature
t Forward shift of switch-on point (h) P
on
Starting point for optimum on
Calibration of sensor
Reset
DIP switch no. 1
Optimum start control
5


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens REV22RF at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens REV22RF in the language / languages: English as an attachment in your email.

The manual is 0,35 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens REV22RF

Siemens REV22RF User Manual - German - 2 pages

Siemens REV22RF User Manual - Dutch - 2 pages

Siemens REV22RF User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info