Siemens Building Technologies CE1N2252E / 14.01.1999
Landis & Staefa Division 5/8
OPTIMUM P.1
OFF
1h / °C
1/2h / °C
1/4h / °C
123
2252Z01
P.1
Optimisation brings forward the switch-on point P.1 such that the selected set point will
be reached at the desired time. The setting depends on the type of control system in
use, that is, on heat transmission (piping system, radiators), building dynamics (building
mass, insulation), and heating output (boiler capacity, flow temperature). The optimisa-
tion is set with DIP switch 1 as follows:
OFF No effect
1/4h/°C For fast controlled systems
1/2h/°C For medium controlled systems
1h/°C For slow controlled systems
t
T
17
18
19
- 4
- 2
2252D01
16
- 3
1/4h/°C
1/2h/°C
1h/°C
P.1
- 2
- 1
- ½
- 1½
- 1
- ½
- ¼- ¾
P
on
20
°C
T1
- 1
h
h
h
TR
x
h
h
h
h
h
h
h
h
h
T Temperature (°C) TR
x
Actual value of room temperature
t Forward shift of switch-on point (h) P
on
Starting point for optimum on
16...29°C
3...29°C
123
2252Z02
COOLING
HEATING
PUMP ON
PUMP OFF
When using minimum limitation of set point to 16 °C, undesired heat transfer to neigh-
bouring flats is prevented in buildings that have several heating zones. The function can
be selected with DIP switch 2.
DIP switch 2 is used for switching over to cooling mode when used in cooling applica-
tions.
The setting is made with DIP switch 2 while the pump is running. Protects the pump
against seizure during longer OFF periods. The periodic pump run is activated for one
minute every 24 hours at 12:00 h.
Technical features
DIP switch 1
Optimum start control
DIP switch 2
Limitation of set point
Cooling
Periodic pump run
(pump kick)
5


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens REV 22 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens REV 22 in the language / languages: English as an attachment in your email.

The manual is 0,43 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens REV 22

Siemens REV 22 User Manual - Dutch - 2 pages

Siemens REV 22 User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info