Siemens RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation CE1P3076.en
Building Technologies Functions 19 Jun 2009
The thermostat can control a 1-speed or 3-speed fan (selected via control
parameter P53). A 1-speed fan is connected to terminal Q1, a 3-speed fan to
terminals Q1, Q2 and Q3.
RDG160 has a DC 0…10 V output for electronically commutated (ECM) fan
motors. The switching points can be set via parameter P55…P57.
w Room temperature setpoint
Q Fan speed
Y
H
Control demand “Heating”
Y
C
Control demand “Cooling”
XpH Proportional band “Heating”
XpC Proportional band “Cooling”
X
dz
Dead zone
S
Fan
Switching point fan (P57)
S
Fmin
ECM fan min. output (P56)
w
XpH
Y
C
[%]
Q [%]
100
Y
H
[%]
0
0
XpC
100
100
x
dz
3181D109
S
Fan
S
Fan
S
Fmin
S
Fmax
S
Fmax
ECM fan max. output (P55)
The diagram only shows the PI controller’s proportional part.
Fan speed 1 = S
Fmin
Fan speed 2 = half-way between S
Fmin
and
S
Fmax
Fan speed 3 = S
Fmax
w
Y
C
[%]
Q [%]
100
Y
H
[%]
0
0
100
100
3181D110
S
Fan
S
Fan
S
Fmin
S
Fmax
Fan III
Fan II
Fan I
=
=
Note: The control signals
"Heating" and "Cooling" are
not influenced by the ma-
nual setting of fan speeds.
Fan operation can be limited to be active with cooling only or heating only, or even
be totally disabled via control parameter “Fan operation” P52.
When fan operation is disabled, the fan symbol on the display disappears and
pressing the fan button has no influence.
This function allows you to use the thermostat on universal applications such as
chilled / heated ceilings and radiator, etc. (see sections 4.7.9 ff).
In automatic
mode, a dwelling time of 2 minutes (factory setting) is active. The fan
maintains each speed for at least 2 minutes before it changes to the next speed.
This minimum on-time can be adjusted from 1…5 minutes via parameter P59.
In automatic fan mode and with the room temperature in the dead zone, the control
valve is normally closed and the fan disabled. With the fan kick function, the fan
can be released from time to time at low speed for minimum on-time (see above)
even if the valve is closed.
This function can be used to avoid damage from moisture due to a lack of air circu-
lation, or to allow a return air temperature sensor to acquire the correct room
temperature.
1-speed / 3-speed fan
Control sequence
for modulating fan
(ECM fan)
Note:
Manual operation
(ECM fan)
Fan operation as per
heating / cooling mode,
or disabled
Fan minimum
on- time
Fan operation in dead
zone (fan kick)
38


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDG100T at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDG100T in the language / languages: English as an attachment in your email.

The manual is 3,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDG100T

Siemens RDG100T User Manual - German - 64 pages

Siemens RDG100T User Manual - Dutch - 2 pages

Siemens RDG100T User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info