Siemens RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation CE1P3076.en
Building Technologies Functions 19 Jun 2009
2. When the thermostat calculates the positions "fully close" or "fully open", the
actuator's running time is extended + 150% to ensure the right actuator
position is synchronized to the control algorithm.
3. After the actuator reaches the position calculated by the thermostat, a waiting
time of 30 seconds is applied to stabilize the outputs.
This function is available with RDG100 and RDG100T only.
The demand calculated by PI control from the current room temperature and set-
point is provided via Y1 and Y3 to the valve actuator as a PWM signal (pulse width
modulation) for thermal actuators. The output is activated for a period proportional
to the heating / cooling demand and then switched off for the rest of the PWM
interval.
The interval is 150 seconds (factory setting). It can be adjusted via parameters
P44 (Y1) or P45 (Y3). These parameters are only visible if 2-position is selected via
DIP switches 4 and 5 and if PWM is selected via P46 and P47.
For thermal valve actuators, set the running time to 240 seconds.
Never apply PWM to an electromotoric actuator
It is not possible to ensure exact parallel running of 2 or more thermal valve
actuator. If several fan coil units are driven by the same thermostat, preference
should be given to electromotoric actuators
For electrical heaters, set the running time to 90 seconds.
To avoid burn-off of mechanical contacts by frequent switching, use a current valve
in place of a relay or contactor.
This function is available with RDG140 and RDG160 only.
The demand calculated by PI control from the current room temperature and
setpoint is provided via Y10 and Y20 to the valve actuator as a continuous
DC 0...10 V signal.
The demand calculated by PI control from the current room temperature and
setpoint is provided via Y20 as a continuous DC 0...10 V signal.
The signal converter (SEM61.4) converts the DC 0...10 V signal to AC 24 V
PDM pulses for the current valve.
The current valve (SEA45.1) supplies the electrical heater with AC 50…660 V
pulsed current.
YE
DC 0 ... 10 V
Y1 G
L
N
Y1 L
Q
5.7 kW
max.
N1
U1
FF
F...
Y1
K...
G0
G
G
3181D21
G
G0
Y
PWM
AC 24 V
N1 RDG140, RDG160
U1 Signal converter SEM61.4 (see Data Sheet N5102)
Y1 Current valve SEA45.1 (see Data Sheet N4937)
K… Safety loop (e.g. safety thermostat and high-
temperature cutout)
FF Very fast-acting fuse
F… Overcurrent trip
PWM control
PWM for thermal
valve actuators
Note!
PWM for electrical
heaters
DC 0...10 V control
DC 0...10 V
for valve actuators
DC 0...10 V
for electrical heaters
36


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDG100T at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDG100T in the language / languages: English as an attachment in your email.

The manual is 3,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDG100T

Siemens RDG100T User Manual - German - 64 pages

Siemens RDG100T User Manual - Dutch - 2 pages

Siemens RDG100T User Manual - French - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info