Siemens RDF301, RDF301.50, RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2012-10-04
The “Floor temperature limitation” function influences the outputs listed in the table
below:
“Floor temp. limit” function has impact on
Application Output Y11 Output Y21
Heating
(P01 = 0/2/3)
Cooling
(P01 = 1/2/3)
Heat. and cool
.
(P01 = 4)
Remark
2-pipe H/C valve Y11 N/A
2-pipe & el heater H/C valve El heater Y21 Y21 *) Only el heater
4-pipe Heating valve Cooling valve Y11 N/A Y11
*) If P13 = ON
electric heater in cooling mode
Either floor temperature sensor or external room temperature sensor can be used.
Dew point monitoring is essential to prevent condensation on the chilled ceiling
(cooling with fan disabled, parameter P52). It helps avoid associated damage to
the building.
A dew point sensor with a potential-free contact is connected to multifunctional
input X1 or X2. If there is condensation, the cooling valve is fully closed until no
more condensation is detected, and the cooling output is disabled temporarily.
The condensation symbol “
” is displayed during temporary override and the fault
“Condensation in room” will be sent via bus.
The input must be commissioned accordingly (P38, P40).
See section 3.9 “Multifunctional input”.
If the “Button
lock” function is enabled by parameter P14, the buttons will be locked
or unlocked by pressing the operating mode button for 3 seconds.
If “Auto lock” is configured, the thermostat will automatically lock the buttons 10 /
20 seconds after the last adjustment (RDF301... / RDF600KN).
Note
Dew point monitoring
KNX
R
Fault state
Fault information
Button lock
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDF301 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDF301 in the language / languages: English as an attachment in your email.

The manual is 2,58 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDF301

Siemens RDF301 User Manual - German - 2 pages

Siemens RDF301 User Manual - French - 2 pages

Siemens RDF301 Installation Guide - All languages - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info