555884
25
Zoom out
Zoom in
Previous page
1/82
Next page
25 / 82
Siemens RDF301, RDF301.50, RDF600KN Basic documentation CE1P3171en
Building Technologies Functions 2012-10-04
3.5 Additional functions
The heating / cooling changeover information can be received via bus. This is only
possible if the control sequence is set to automatic heating / cooling changeover
(parameter P01 = 3) and no local input X1, X2 is assigned with this function.
In the absence of the required information (e.g. due to problems with data
communication, power failure, etc.), the thermostat operates in the last valid room
operating mode (heating or cooling).
If a cable temperature sensor (QAH11.1 + ARG86.3) is connected to X1 / X2, and
parameter P38 / P40 is =2, the water temperature acquired by the changeover
sensor is used to change over from heating to cooling mode, or vice versa. When
the water temperature is above 28 °C (parameter P37), the thermostat changes
over to heating mode, and to cooling mode when below 16 °C (parameter P36).
If the water temperature is between the 2 changeover points immediately after
power-up, the thermostat starts in the previously active mode.
The water temperature is acquired at 30-second intervals and the operating state is
updated accordingly.
16
M
T
w
[°C]
28
M Operating mode
Cooling mode
T
w
Water temperature
Heating mode
The QAH11.1 cable temperature sensor for automatic heating / cooling changeover
can be replaced by an external switch for manual, remote changeover:
3076Z03
X2
M
T
X2
M
QAH11.1
T °C
Contact open heating mode
Contact closed cooling mode
The sensor or switch can be connected to input terminal X2 or X1, depending on
the commissioning of the inputs (P38, P40).
See also section 3.9 “Multifunctional input”.
If manual hea
ting / cooling changeover is commissioned (P01 = 2), then heating /
cooling mode cannot be changed via bus / changover sensor / switch; it will remain
in the last mode as selected locally via button.
The thermostat acquires the room temperature via built-in sensor, external room
temperature sensor (QAA32), or external return air temperature sensor (QAH11.1)
connected to multifunctional input X1 or X2.
Inputs X1 or X2 must be commissioned accordingly. See section 3.9 “Multi-
func
tional input”.
Heating / cooling
changeover via bus
KNX
R
Heating/cooling
changeover
Automatic heating /
cooling changeover via
changeover sensor
Changeover switch
Manual heating /
cooling changeover
External / return air
temperature sensor
25


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens RDF301 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens RDF301 in the language / languages: English as an attachment in your email.

The manual is 2,58 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Siemens RDF301

Siemens RDF301 User Manual - German - 2 pages

Siemens RDF301 User Manual - French - 2 pages

Siemens RDF301 Installation Guide - All languages - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info