10.3
Device Test
Smoke detector
1. Enable t
est mode for the zone
2. Place
detector
3.
Wait until LED is on
4.
Remove testing unit
Automatic
5.
Set zone to
Heat detector
1. Enable t
est mode for the zone
2. Place
detector
and turn on heater.
3.
Wait until LED
4.
Remove testing unit
Automatic reset of test alarm after 15 sec.
5.
Set zone to normal mode operation.
Manual call point
1. Enable t
est mode for the
2.
Depending on type of call point, insert test key or
open cover to activate
3.
Wait until LED is on
4.
Remove test key or close door
Automatic reset of test alarm after 15 sec.
5.
Set zone to normal mode operation.
10.4
Completion work
1.
Activate a test alarm through the system operator with remote transmission.
2.
Disable all
3. Have
system owner confirm
Device Test
Smoke detector
est mode for the zone
.
detector
tester RE6 or RE8ST on detector head.
Wait until LED is on
– Sounder sounds 1 sec.
Remove testing unit
-
Automatic
reset of test alarm after 15 sec.
Set zone to
normal mode operation
.
est mode for the zone
.
detector
tester RE6T or RE7T on detector head
and turn on heater.
Wait until LED
is on – Sounder sounds 1 sec.
Remove testing unit
-
Automatic reset of test alarm after 15 sec.
Set zone to normal mode operation.
Manual call point
est mode for the
zone.
Depending on type of call point, insert test key or
open cover to activate
.
Wait until LED is on
- Sounder sounds 1 sec.
Remove test key or close door
-
Automatic reset of test alarm after 15 sec.
Set zone to normal mode operation.
Completion work
Activate a test alarm through the system operator with remote transmission.
Disable all
'OFF' status.
system owner confirm
the revision.
77
Activate a test alarm through the system operator with remote transmission.
79


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens FC123-ZA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens FC123-ZA in the language / languages: English as an attachment in your email.

The manual is 3,88 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info