Building Technologies A6V10393190_c_en_--
Fire Safety
2014-05-28
- Configure
Output
Output 4 – n
Mode
Sounder control
Functionality 'Supervised line':
The panel monitors the line in terms of open and short circuits from the panel to the
EOL element.
In addition to the line monitoring, the panel will recognize a change of line resistance.
Due to aging or other circumstances (creeping effect), the transition resistance on
contacts may increase, which in turn leads to voltage drop.
In order to detect the creeping effect (supervision), the line must be calibrated during the
commissioning process. A line fault is indicated if the resistance is higher than 35
.
Checking the line resistance depending on the required current
It is calculated that the supply of the connected devices is met.
The picture shows the dependence of the line resistance (R Line) in relation to the device
voltage (U
min
) and the available output current (
I
max
) and the minimum required current of
the connected devices (
I
Load).
Procedure for determining the maximum available device current (
I
Load):
1) Determine the line resistance R Line.
Programming: see chapter 7.2.1 (Calibration)
Configure
Output
Output 4 – n
Calibrate line
2) Detecting the voltage U
min
according to the device datasheet.
3) Verification: Are all parameters satisfied for the correct operations?
Table 1 can be used for this check, here are maximum values shown.
Details are individual to calculate.
Table 1
I
max
R Line
U
min
= 9 V U
min
= 14.5 V U
min
= 16.8 V U
min
= 18 V
1 A 0 ~ 7
0 ~ 3.5
0 ~ 2
0 ~ 1
0.5 A 0 ~ 14.5
0 ~ 7.5
0 ~ 4.5
0 ~ 3
0.3 A 0 ~ 25
0 ~ 13
0 ~ 8
0 ~ 5.5
0.1 A 0 ~ 35
0 ~ 35
0 ~ 26
0 ~ 18.5
0.05 A 0 ~ 35
0 ~ 35
0 ~ 35
0 ~ 35
Counteractive measures: Reduction of
I
Load or of R Line.
Functionality 'Supervised line for fault dialer and relay':
The line is supervised, from the terminal including the activated relay in the fault dialer, in
terms of open and short circuit. In addition to the line supervising, the panel will recognize
OUT A
R Line
EOL
Load
28


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens FC122-ZA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens FC122-ZA in the language / languages: English as an attachment in your email.

The manual is 3,88 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info