INSTRUCTION MANUAL OF THE SIEMENS CLIMATIX 2 CONTROL EQUIPMENT
-
41
-
The line OFF cascade defines the limit when the boilers in the cascade are deactivated based on
the value of the temperature B10.
The line Cascade power defines the actual state of the required cascade power. It can range from
0 to 100% and the number of the boilers in the cascade can vary.
The line Absolute cascade power defines the absolute required power expressed as a
percentage. Its range depends on the actual number of boilers in the cascade, e.g. if 2 boilers are
in the cascade, the range is 0 to 200%; if 4 boilers are in the cascade, the range is 0 to 400%.
The line K1 diagnostics informs about the actual state of boiler K1 in the cascade. Its power, state
(Released/Not released/Put out of operation/Out of service).
The line Demand active states whether the appliances’ demand (of heating circuits and of DHW)
is active or inactive in the respective boiler K1.
K2 diagnostics, K3 diagnostics, K4 diagnostics – see K1 diagnostics.
The line Sequencing priority informs about the principles of boilers sequencing in the cascade.
The mode Auto means that the switching is automatic according to the operating hours. If a
specific boiler is displayed, it means that it is permanently placed as the first one in the cascade.
The line Actual sequencing states which of the boilers is placed as the first one at the moment.
The line Actual time states how much time has passed since the last sequencing switched in the
cascade.
The line Sequencing period informs about the required interval of the sequencing change in the
cascade.
The line Time to change cascade priority informs about the time when the sequencing in the
cascade changes.
6.11. DIAGNOSTICS OF SOURCE
This file includes all information about the source, i.e. about the boiler and the buffer storage tank.
After clicking on the line Diagnostics of boiler it is possible to enter the site where all basic
information about the boiler operation is summarized:
State of boiler Out of operation / Operation / Reduce from
temperature /
External reduce / etc.
Actual required temperature °C
Temperature boiler ON °C
Temperature boiler OFF °C
After clicking on the line Diagnostics of buffer it is possible to enter the site where all basic
information about the buffer storage tank is summarized:
Buffer Charging active / Charged
Top buffer B4 boiler ON °C
41


Need help? Post your question in this forum.

Forumrules
1

Forum

siemens-climatix-2

Reset search

  • salve
    chiedo se è possibile fare un by pass per far partire il sistema di condizionamento a causa dell'oscuramento :del controllore POL/STD
    grazie
    Submitted on 11-3-2022 at 12:44

    Reply Report abuse


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Siemens Climatix 2 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Siemens Climatix 2 in the language / languages: English as an attachment in your email.

The manual is 1,35 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info