489454
38
Zoom out
Zoom in
Previous page
1/77
Next page
38
10. TROUBLESHOOTING
Precautions before performing inspection or repair
NOTE
Executing self-diagnostics
After checking the self-diagnostics monitor, turn the power OFF before starting inspection or repair.
High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge
(charging voltage DC 310 V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be
careful not to touch any electrified parts before the controller LED (red) turns OFF.
If the outdoor controller is normal, approximately 30 seconds will be required for the charge to dissipate. However, allow at
least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller.
1: If the operation lamp blinks every 0.5 seconds immediately when the power
is turned ON, there is an external ROM (OTP data) failure on the indoor
circuit board, or a ROM socket insertion problem, or the ROM has not been
installed.
2: The failure mode is stored in memory even when the power is not ON.
Follow the procedure below to perform diagnostics.
Method of self-diagnostics
Follow the procedure below to perform detailed trouble diagnostics.
ON
E
I/OFF
E
1HR.
UIET
MODE
TEMP.
TIMER
CANCEL
SENSOR
ADR ACL
24H12HF
CLOCK
NIGHT SETBACKFAN SPEED
HIGH POWER
FLAP
AIR CONDITIONER
1HR.
TIMER
button
ON/OFF
operation
button
ACL
(Reset)
button
QUIET
button
< Clock display >
Test run mode
Self-diagnostics mode
Step 1: Press and hold the remote controller QUIET button and 1 HR TIMER
button. At the same time, press the ACL (reset) button. Use a pointed
object such as the tip of a pen to press the ACL button.
When this has been done, “oP-1” (test run) appears, blinking, in the
remote controller clock display area.
Step 2: Next, press the 1 HR TIMER button once to change the display from
“oP-1” to “oP-3” (self-diagnostics). (The display continues to blink.)
Step 3: Finally press the ON/OFF button to engage self-diagnostics mode.
• The self-diagnostics function utilizes the 3 indicator lamps on the main unit, in
combinations of ON lamps, blinking lamps, and OFF lamps, to report the
existence of sensor trouble or a protective operation. (The lamps blink or
remain ON for 5 seconds, then turn OFF for 2 seconds.) Self-diagnostics is
completed when the buzzer sounds 3 short beeps.
• A maximum of 3 self-diagnostics reports are displayed, for 5 seconds each,
beginning with the most recent report. Following this display the lamps turn
OFF. In order to view the self-diagnostics results again, press the ON/OFF
button again.
• The 3 lamps remain OFF if no trouble has occurred.
<IMPORTANT> After self-diagnostics is completed, be sure to press the ACL
(reset) button to return to normal mode. The air conditioner will
not operate if this is not done.
After turning on power to the air conditioner, use the remote controller and
follow the steps below to execute self-diagnostics.
38


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sanyo SAP-KRV123EH at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sanyo SAP-KRV123EH in the language / languages: English as an attachment in your email.

The manual is 2,36 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info