Heating operation
Frost sensing
Reverse-cycle defrosting operation
Defrosting Sequence
Releasing of defrosting
Outdoor fan ON
4-way valve ON
Outdoor heating exchanger temp. is over 14°C.
Defrosting operation lasts 12 minutes (maximum).
2 minutes after it is stopped, compressor is ON.
4-way valve is ON. Outdoor fan is ON.
If the air conditioner is turned off during the defrosting
cycle, it will continue defrosting and turn itself off after
defrosting is completed.
Compressor
1 minute after it is stopped,
compressor is ON.
Outdoor fan
OFF
Indoor fan
OFF
4-way valve
OFF
Operation lamp
Reverse-Cycle Defrosting
NOTE
Defrost detection and release
This function prevents the circuit breaker or fuse from operating
to open the circuit. This function works when electrical current
has increased due to an increase in the cooling / heating load,
or to a decrease in the power supply voltage. In these cases,
operation frequency is reduced or operation is interrupted auto-
matically to control the electrical current for operation.
When the cause of the increase in electrical current is rectified,
the system will resume operation in the original mode.
Electrical current setting for COOL operation is
used during DEFROST operation.
Cooling • Dry Heating
Peak current cut-off trips 12.0
Hz down 8.5 8.5
NOTE
(A)SAP-KRV93, KRV123
CT (Peak current cut-off control)
Repeatedly switches between red
and orange illumination.
Defrost detection occurs in either of the following cases:
The temperature of the heat exchanger remains at
or below the L2 line for 120 minutes after the start
of HEAT operation.
Outdoor heat
exchanger temp.
Ambient temp.
0
L1
L2
Frosting area
The temperature of the heat exchanger remains at
or below the L1 line for 3 minutes after the start of
HEAT operation.
37


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Sanyo SAP-KRV123EH at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Sanyo SAP-KRV123EH in the language / languages: English as an attachment in your email.

The manual is 2,36 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info