Measure the gas pressure at the supply side of the gas valve. This must be at least 18 or 35 mbar
(for natural gas) with the boiler operating at full capacity. When multiple appliances are installed
in the boiler room, this pressure must be measured with all the appliances operating at full capac-
ity.
Check the temperature difference (∆T) between the fl ow and return to the appliance at the water
side. ∆T must be between 15 and 25 K at full capacity.
Check the appliance at minimum capacity
Adjust the appliance to operate at minimum capacity. At mini mum capacity the following settings
must be checked and corrected if necessary:
Pilot burner CO
2
[%] 10.2 ± 0.2
Pilot burner CO [ppm] ≤ 1000
Main burner CO
2
[%] 9.3 ± 0.2
Main burner CO [ppm] ≤ 30
Burner pressure p
fan
– p
above burner
[mbar] 0.7 ± 0.1
Propane
Pilot burner CO
2
[%] 11.0 - 11.4
Pilot burner CO [ppm] ≤ 1000
Main burner CO
2
[%] 10.8 - 11.2
Main burner CO [ppm] ≤ 30
Burner pressure p
fan
– p
above burner
[mbar] 0.7 ± 0.1
Table 16 Settings at minimum capacity
Setting air pressure switch: 0,4 ± 0,05 mbar
Check the function ∆P
min
pressure switch by carefully placing a board (for example, a piece of
strong cardboard) in front of the supply opening to the fan and slowly slide the board so as to
close off the opening until the boiler shuts down.
If the appliance is checked in the manner indicated, and cor rected as necessary, the following
pressures, at full capacity, must be recorded for reference on the commissioning report note:
P
vent
P
bb
P
vent
-P
bb
(measure separately!)
P
vh
∆T
8 Maintenance
8.1 Safety
During maintenance activities, always wear suitable clothing and shoes. Consider your own
safety, particularly in respect of jewellery and loose clothing.
8.2 General
In order to ensure continued good and safe operation of the appliance, this must be inspected at
least once per year.
47


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Rendamax R3500 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Rendamax R3500 in the language / languages: English as an attachment in your email.

The manual is 1,8 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info