The unit has been manufactured using state-of-the-art production methods and has been tested several times
to ensure that it works properly. If malfunctions should occur, please check the unit as detailed in the list
below. Please inform your dealer if the unit is still not working correctly after all the function checks have been
performed.
Troubleshooting and customer service
Operational malfunctions
Please note that this troubleshooting table continues on the next pages
Malfunction Possible cause Checks Remedial measures Major
P01 Medium inlet probe defective
- Check:
- Probe resistance
- Connections of the probe cable
- Replace defective probe
- Renew connections
P02
Medium outlet sensor
defective
- Check:
- Probe resistance
- Connections of the probe cable
- Replace defective probe
- Renew connections
P04
Probe defective, ambient
temperature probe
- Check:
- Probe resistance
- Connections of the probe cable
- Replace defective probe
- Renew connections
P07
Probe defective, suction gas
temperature probe
- Check:
- Probe resistance
- Connections of the probe cable
- Replace defective probe
- Renew connections
P08
Probe defective, heat gas
temperature probe
- Check:
- Probe resistance
- Connections of the probe cable
- Replace defective probe
- Renew connections
PP1 "Low-pressure probe fault"
- Check:
- Probe resistance
- Connections of the probe cable
- Replace defective probe
- Renew connections
PP2 "High-pressure probe fault"
- Check:
- Probe resistance
- Connections of the probe cable
- Replace defective probe
- Renew connections
E01
High-pressure switch, high-
pressure alarm
In cooling mode:
Finned heat exchanger
blocked, dirty or exposed to
excessive sunlight? Condenser
fan or high-pressure switch
defective?
In heating mode:
Medium flow rate too low,
Medium temperature on
the plate heat exchanger too
high, High-pressure switch
defective.
In cooling mode:
Clear finned heat exchanger,
clean, shade, have condenser
fan checked by specialist
personnel, check high-
pressure switch.
In heating mode:
Check medium flow rate and
medium temperature, check
high-pressure switch
X
E02
Low-pressure probe low-pres-
sure alarm
In cooling mode:
Insufficient refrigerant,
Medium flow rate too low,
low-pressure switch defective.
In heating mode:
Insufficient refrigerant,
Finned heat exchanger
blocked or dirty? Evaporator
fan or low-pressure switch
defective?
In cooling mode:
Insufficient Refrigerant, check
medium flow rate and low-
pressure switch.
In heating mode:
Clear and clean finned heat
exchanger, have evaporator
fan checked by specialist
personnel, check low-pressure
switch.
X
37
37


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO RVS DC serie 50-80-130-180 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO RVS DC serie 50-80-130-180 in the language / languages: English as an attachment in your email.

The manual is 3,08 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO RVS DC serie 50-80-130-180

REMKO RVS DC serie 50-80-130-180 User Manual - German - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info