Observe the manuals
for the unit and all other
components when
commissioning the entire
system.
Commissioning should only be
performed by specially trained
personnel and documented
after the certificate has been
issued.
NOTE
Commissioning
Functional test for
Cooling mode:
1. Switch the power supply on.
2. Open all shut-off valves
if necessary.
3. Switch the unit and
the corresponding circulation
pump on to the highest level.
The outlet temperature must
be between +4 and +18°C.
4. Switch the unit on and select
the cooling operating mode.
If the return temperature
is warmer than the setting,
the compressor display will flash
and the compressor will begin
to work after approx. 3 to
5 minutes.
5. Please note that the inlet
temperature at the nominal
flow rate of the medium lies
approx. 5 K below the return
temperature.
- If the supply temperature falls
below the factory setting of
4°C, a fault triggers.
If this is the case, a higher
return temperature must be
selected. If the spread is too
great or too small, the medium
flow rate must be checked.
- The circulation pump starts
and the controller checks
the medium flow rate via
the differential pressure/flow
switch.
If the volume is insufficient,
a fault shut-off will be carried
out and the cooling cycle will
not be enabled.
6. Measure and record all
the required values in
the commissioning report and
check the safety functions.
7. Check the unit control system
using the functions described
in the "Operation" chapter.
Functional test for
Heating mode
1. Switch the power supply on.
2. Open all shut-off valves if
necessary.
3. The voltage supply is made
at the chiller; a control cable
to the interior unit is not
necessary.
The outlet temperature must be
between +35 and +45°C.
4. Switch the unit on and select the
heating operating mode.
If the return temperature
is colder than the setting,
the compressor display will
flash and the compressor will
begin to work after approx.
3 minutes.
5. Please note that the supply
temperature at the nominal
flow volume of the medium
lies approx. 5 K above
the return temperature.
- The circulation pump starts
and the controller checks
the medium flow rate via
the differential pressure/flow
switch.
If the volume is insufficient,
a fault shut-off will be carried
out and the cooling cycle will
not be enabled.
6. Measure and record all
the required values in
the commissioning report
and check the safety functions.
7. Check the unit control system
using the functions described
in the "Operation" chapter.
Final tasks
Reassemble all disassembled
parts.
Familiarise the operator
with the system.
35
35


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO RVS DC serie 50-80-130-180 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO RVS DC serie 50-80-130-180 in the language / languages: English as an attachment in your email.

The manual is 3,08 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO RVS DC serie 50-80-130-180

REMKO RVS DC serie 50-80-130-180 User Manual - German - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info