Anti-freeze protection (accessories)
As a medium for a cold water
system, a water-glycol mixture
is used as a rule. Depending on
the use to which the glycol type
and quantity is put, the viscosity
changes, the loss in pressure
increases and the unit's cooling
or heating capacity reduces.
All system components must be
approved for use with glycol.
As a rule, the addition to the
water of ethylene glycol, in a
proportion of 34%, with inhibitors
for corrosion protection is
recommended.
Diaphragm expansion vessel (MAG)
To avoid pressure fluctuations
during standstill because of
temperature changes, diaphragm
expansion vessels filled with
nitrogen (moisture neutral) must
be integrated in the system.
Safety valve
Safety valves limit excess operating
pressure due to excess warming
or overfilling of the operating
medium. The valve outlet requires
unobstructed draining into a drain
line. Applicable local disposal
ordinances must be observed
if glycol is used.
The standard scope of delivery
for the unit includes a safety
valve; an additional valve may
be necessary at a suitable point.
Compensators
Compensators are used to connect
lines to the unit to prevent vibration
in the chiller from transmitting
to other system components.
Compensators
Shut-off valve Compensator
Static fasten-
ing
Unit connection
Air bleeding valves
The unit has manual air bleeding
valves. The unit can be bled here
after the system has been filled.
Automatic bleeding valves must
also be installed at the highest
point in the collector line.
Dirt trap
A rinsable dirt trap must be
installed upstream from the unit
intake. The mesh size should not
be less than 10 mesh/cm². Shut-
off valves should be installed
upstream and downstream from
the dirt trap.
External medium storage tank
If, for example, the required
capacity of the cold water
consumer is significantly less
than the cooling capacity
generated by the chiller, an
increase in the medium content
is recommended. As an example,
the medium piping can be
oversized or an additional
storage tank installed to increase
compressor operating time.
A storage tank should, as a rule,
be provided if the minimum
medium volume is not reached.
Shut-off valves
As a rule, in cold water systems,
shut-off valves with full admission
should be used. For the purpose
of servicing, medium inlet and
medium outlet must be equipped
with shut-off valves (if necessary
safety valves).
Glycol-tolerant air bleeding
valves are necessary when
using media that contain
glycol.
CAUTION
!
Improperly installed or missing
dirt traps can cause fouling
of the plate heat exchanger.
CAUTION
!
During use and
disposal, product and safety
data sheets for the glycol
type being used as well
as applicable local ordinances
(e.g. Water Resources Act)
must be observed.
CAUTION
!
Use the required type and
mix ratio appropriate for
the application area to ensure
the freezing point.
CAUTION
!
23
23


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO RVS DC serie 50-80-130-180 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO RVS DC serie 50-80-130-180 in the language / languages: English as an attachment in your email.

The manual is 3,08 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO RVS DC serie 50-80-130-180

REMKO RVS DC serie 50-80-130-180 User Manual - German - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info