Fault Possible cause Check Remedial measures
The unit is running
with reduced or
without cooling or
heating output
Filter is dirty / air inlet / outlet
opening is blocked by by debris Have the filters been cleaned? Clean the filters
Doors and windows open /
heating or cooling load was
increased
Have there been any
constructional / application-
related changes?
Close doors and windows /
install additional systems
Neither cooling nor heating
mode has been set
Does the "cooling / heating"
symbol appear in the display? Correct the settings for the unit
Fins of outdoor unit are blocked
by debris
Is the fan on the outdoor
unit running are the fins
unobstructed?
Check fan or winter regulation,
reduce air resistance
Leaking refrigerant circuit Are there signs of frost on the
fins of the indoor unit? Repair by a specialist
Condensation
output on the unit
Drain pipe of the collection
container blocked / damaged
Is unobstructed condensation
drainage ensured?
Clean the drainage pipe and
collection container
Faulty external condensation
pump or float
Is the condensation pan full
of water and the pump is not
working?
Call out a specialist to replace the
pump
Condensation has not drained
away and has collected in the
condensation line
Is the condensation line routing
sloped downhill and is it clear?
Route the condensation line in
a downhill slope or clean it if
necessary
Condensation does not drain
off
Are the condensation lines
unblocked and is there a steady fall?
Are the condensation pump and
oat switch functioning correctly?
The condensation line must have
a fall. If necessary, clean the pipe.
A faulty condensation pump and
float switch should be replaced.
Leaking refrigerant circuit Are there signs of severe frost
on the large stop valve? Repair by certified service centre.
Problem display by blinker code
Display Cause Required action
E0 EEPROM error
Switch off the power to device for
1 min.
Contact specialist dealer
E1 Communication error between outdoor unit and indoor unit Contact specialist dealer
E2 Phase monitoring has responded Check wiring
E3 Evaporator fan motor speed too low / defective Contact specialist dealer
E5 Sensor discharge hot gas AT faulty / connection interrupted Check connection and plug
E6 Sensor recirculated air IT faulty / connection interrupted Check connection and plug
P0 Rotational speed monitoring on compressor has responded
(Inverter module)
Check connections CN4, CN1 on the AT
PCB / contact specialist dealer
P1 Overvoltage protection AT tripped (250V) Check the voltage of the mains cable
P2 Excessive temperature (Klixon) compressor has tripped
Check refrigerant
Check the resistance of the compressor
sensor (normal 0Ω)
P3 Overcurrent compressor has responded Check winding resistance of the com-
pressor (1Ω = U-V / U-W / V-W)
REMKO MXW
18
18


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO MXW520 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO MXW520 in the language / languages: English as an attachment in your email.

The manual is 1,74 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO MXW520

REMKO MXW520 User Manual - German - 28 pages

REMKO MXW520 User Manual - Dutch - 28 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info