Function test of cooling operating mode
1. Remove the protective caps from the valves.
2. Start the commissioning procedure by briefly
opening the shut-of
f valves on the outdoor
unit until the pressure gauge indicates a
pressure of approx. 2 bar.
3. Check all connections for leaks with leak
detection spray and suitable leak detectors.
4. If no leaks are found, fully open the shut-of
f
valves by turning them anti-clockwise using a
spanner. If leaks were found, draw off the
refrigerant and rework the defective connec-
tion. It is imperative that the vacuum creation
and drying steps are repeated!
5. Activate the main circuit breaker or fuse.
6. Use the remote control to set the indoor
unit's target temperature to a value that is
lower than the existing room temperature.
Due to the turn on delay
, the compressor
will start up a few minutes later.
7. Switch the indoor unit to cooling mode.
8. Check all regulating, control and safety
devices for function and correct adjustment
during the test run.
9. Check the control of the indoor unit with the
functions described in the operating instruc-
tions: timer
, temperature adjustments and all
mode settings.
Check the individual operating parame-
ters with the help of the display on the
outdoor unit as described in the "Func-
tional checks and test run" section, and
note the value in the commissioning log.
10. Measure the overheating, external, internal,
discharge and evaporator temperatures and
record the test data in the commissioning log.
11. Remove the pressure gauge.
12. Proceed as previously described for all other
cooling cycles.
Final tasks
n Use the remote control to set the target tem-
perature to the required value.
n Re-install all disassembled parts.
n Familiarise the operator with the system.
NOTICE!
Check that the shut-of
f valves and valve caps
are tight after carrying out any work on the
cooling cycle. Use appropriate sealant products
as necessary.
Probe description
T1 Room temperature probe for indoor unit
T2 Evaporator centre temperature probe for
indoor unit
T2B Temperature probe for suction pipe
(installed in the outdoor unit)
T3 Temperature probe for condenser outlet
T4 Temperature probe for condenser air inlet
T5 Temperature probe for heat gas line com-
pressor
Ts Setpoint
Outdoor unit display
The digital display is located on the outdoor unit's
control board. This display can be used to show
the current operating status.
n The display shows "- -" in standby
n The display shows the current operating fre-
quency when the compressor is running
n When defrosting, the display shows "dF" or
alternates between "dF" and the current com-
pressor frequency (0.5s each)
n If the compressor is in the pre-heating function,
the display shows "PH" or alternates between
"PH" and the current compressor frequency
(0.5s each)
n If the system's oil return function is running, the
display shows "RO" or alternates between
"RO" and the current compressor frequency
(0.5s each)
n If winter fan speed control is active due to low
outside temperatures, the display shows "LC"
or alternates between the compressor fre-
quency and "LC" (0.5s each)
n In “Force Cool Mode – Force Control”, the dis-
play shows "FC" or alternates between "FC"
and the current compressor frequency (0.5s
each)
REMKO MVT series
34
34


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO MVT 1053 DC at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO MVT 1053 DC in the language / languages: English as an attachment in your email.

The manual is 4,22 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO MVT 1053 DC

REMKO MVT 1053 DC User Manual - German - 78 pages

REMKO MVT 1053 DC User Manual - Dutch - 68 pages

REMKO MVT 1053 DC User Manual - French - 68 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info