Fill and drain connection
A connection should be provided in an area safe
from frost for the draining of pipe lines (especially if
water is used as a medium). Applicable local dis-
posal ordinances must be observed if glycol is
used.
Dirt trap
A rinsable dirt trap must be installed upstream from
the unit intake. The mesh size should not be less
than 10 mesh/cm
2
. Shut-of
f valves should be
installed upstream and downstream from the dirt
trap.
NOTICE!
Improperly installed or missing dirt traps can
cause fouling of the plate heat exchanger
.
External medium storage tank
If, for example, the necessary capacity of the cold
water outlet is significantly less than the cooling
capacity generated by the chiller, an increase in
the medium content is recommended. As an
example, the medium piping can be oversized or
an additional storage tank installed to increase
compressor operating time. A storage tank should,
as a rule, be provided if the minimum medium
volume is not reached.
NOTICE!
Malfunctions can result if the flow rate drops
below the minimum medium volume.
7 Condensate drainage
connection and safe
drainage
Condensate drainage connection
If the temperature falls below the dew point, con-
densation will form on the finned condenser during
heating mode.
A condensate tray should be installed on the
underside of the unit to drain any condensate.
n The condensate drainage line should have an
incline of min. 2%. This is the responsibility of
the customer
. If necessary, fit vapour-diffusion-
proof insulation.
n When operating the unit at outdoor tempera-
tures below 4 , care must be taken that the
condensate drainage line is anti-freeze pro-
tected. The lower part of the housing and con-
densate tray is also to be kept frost free in
order to ensure permanent draining of the con-
densate. If necessary, fit a pipe heater.
n Following installation, check that the conden-
sate run off is unobstructed and ensure that the
line is durably leak tight.
2
1
1: Condensate tray
2: Condensate drainage
Safe drainage in the event of leakages
Local regulations or environmental laws, for
example the German W
ater Resource Act (WHG),
can require suitable precautions to protect against
uncontrolled drainage in case of leakage to provide
for safe disposal of escaping air conditioning fluid
or hazardous media.
REMKO KWE
44
44


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO KWE serie 150-180-220-250-300-320-370-440 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO KWE serie 150-180-220-250-300-320-370-440 in the language / languages: English as an attachment in your email.

The manual is 2,8 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO KWE serie 150-180-220-250-300-320-370-440

REMKO KWE serie 150-180-220-250-300-320-370-440 User Manual - German - 60 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info