6.3 Necessary system components
Valve assembly (accessory)
In 2-conductor systems, cold or warm medium is
fed through the register in the unit and cold or
warm air can then be released. Control is provide
by the 3-way valve assembly
. It comprises the
electrically actuated valve head and the valve
body. If the head is electrically activated, it
actuates the body, which routes the medium into
the register. If the temperature is reached, the
head is switched off and the medium is fed past
the heat exchanger through the bypass . The
bypass serves to ensure the minimum medium
flow rate for the chiller.
The time between being fully open and fully
closed can be approx. three minutes.
Valves for hydronic balancing
The calculated individual pressure losses in the
pipeline network layout for each individual unit are
adjusted to the entire system with hydronic bal-
ancing valves to be provided by the customer
. The
nominal flow rates for the medium adjust to the
values needed as a consequence of the pressure
loss.
Anti-freeze protection (accessories)
A water glycol mix is generally used as medium for
a cold water system. Depending on the use to
which the glycol type and quantity is put, the vis-
cosity changes, the loss in pressure increases and
the unit's cooling or heating capacity reduces. All
system components must be approved for use with
glycol.
NOTICE!
When disposing, the product requirements of
the glycol type used must be observed.
Diaphragm expansion vessel (MAG)
To avoid pressure fluctuations during standstill
because of temperature changes, diaphragm
expansion vessels filled with nitrogen (moisture
neutral) must be integrated in the system.
No moisture can condense in the nitrogen filler
.
Safety valve
Safety valves limit excess operating pressure due
to excess warming or overfilling of the operating
medium. The valve outlet requires unobstructed
draining into a drain line. Applicable local disposal
ordinances must be observed if glycol is used.
Automatic bleed valves
The unit has one or two manual bleed valves on
the collector pipe of the register
. The unit can be
bled separately after the system has been filled.
Automatic bleeding valves must also be installed at
the highest point in the collector line.
NOTICE!
Glycol tolerant air bleeding valves are neces-
sary when using media that contain glycol.
1
2
3
43
Fig. 34: Manual bleeding
1: Valve body
2: Additional condensate tray
3: Shut-off valve
4: Valve head
REMKO KWD
30
30


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO KWD serie 25-35-45-55-70-85-100 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO KWD serie 25-35-45-55-70-85-100 in the language / languages: English as an attachment in your email.

The manual is 4,47 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO KWD serie 25-35-45-55-70-85-100

REMKO KWD serie 25-35-45-55-70-85-100 User Manual - German - 52 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info