For example: Gas appliance type C:
The combustion system is tight
with respect to the environment in
which it is installed.
The combustion air is supplied
from the outside.
The units must only be operated
with suitable chimney pipes.
The components available as
accessories from the factory
comply with all requirements as
standard.
Condensation
If necessary, the chimney pipes
must be insulated to prevent the
formation of condensation in the
same.
The exhaust gas temperature at
minimum heat output corresponds
approximately to the condensation
temperature.
For pipe lengths above 5 m
indoors and 3 m outdoors,
condensation must be prevented
as follows:
By cladding the chimney pipes
By using condensate drains
from where the collected
condensation can be removed
from the chimney pipe.
Note:
Suitable condensate drains are
available as accessories.
These can be used for both
horizontal and vertical pipes.
Guide for selection
If the chimney end piece is not
connected directly to the unit,
but longer distances have to
be covered, it must be ensured
appropriate to the total length and
geometry of the chimney duct that
the end pieces and extensions as
well as the bends have the correct
diameter.
After determining the chimney
duct, the pressure loss for
the respective unit must be
determined.
The pressure loss varies for each
unit as the exhaust fl ow rate is
output-dependent.
Add up the determined pressure
losses of the individual chimney
components and ensure that the
total is not above the pressure
available for the type of unit to be
used.
If a combustion air supply pipe
exists, the pressure losses must
be added to those of the chimney
pipe.
If the total pressure losses are
above the available unit pressure,
chimney and fresh air pipes with a
larger diameter must be used.
In this case, calculation must be
repeated.
The maximum possible pipe
lengths between the unit and end
piece are shown in the tables.
When using chimney bends,
it is necessary to take the
corresponding pressure losses into
account.
NOTE
Exceeding the permissible
pressure losses in the pipes
will reduce the heat output
and affect the safe operation
of the units.
ATTENTION
Installation must only be car-
ried out by authorised specia-
lists.
Pressure loss examples:
A 90° bend with Ø 80
corresponds to a 1.7 m straight
pipe length
A 45° bend with Ø 80
corresponds to a 0.8 m straight
pipe length
A 90° bend with Ø 100
corresponds to a 1.9 m straight
pipe length
A 45° bend with Ø 100
corresponds to a 0.9 m straight
pipe length
Examples of chimney pipe and
combustion air pipe arrangements
are shown on the following pages.
The units are classifi ed for the
following individual installation
B23/C13/C33/C43/C53/C63
variants:
The use of plastic chimney
pipes must be avoided.
ATTENTION
23


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for REMKO GPM 35 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of REMKO GPM 35 in the language / languages: English as an attachment in your email.

The manual is 4,39 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of REMKO GPM 35

REMKO GPM 35 User Manual - German - 44 pages

REMKO GPM 35 User Manual - Dutch - 44 pages

REMKO GPM 35 User Manual - French - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info