Tab.20 Temperature-based control (°C)
Jumper 2 Input signal (V) Temperature °C Description
0–1.5 0–15 Boiler off
1.5–1.8 15–18 Hysteresis
1.8–10 18–100 Desired temperature
The 0–10 V signal controls the boiler supply temperature. This control
modulates on the basis of flow temperature. The output varies between
the minimum and maximum value on the basis of the flow temperature set
point calculated by the controller.
A jumper (2) on the interface is used to select either temperature-based
control ( ) or output-based control (%).
Tab.21 Control based on heat output
Jumper 2 Input signal (V) Heat output (%) Description
%
0–2.0(1) 0–20 Boiler off
2.0–2.2 (1) 20–22 Hysteresis
2.0–10 (1) 20–100 Desired heat output
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
The 0–10 V signal controls the boiler output. This control modulates on the
basis of the heat output. The minimum output is linked to the boiler's
modulation depth. The output varies between the minimum and maximum
value on the basis of the value defined by the controller.
Analogue output (0–10 V)
This feedback can be based on temperature or heat output. The two
controls are described briefly below.
A jumper (1) on the interface is used to select either temperature ( ) or
output (%).
Tab.22 Temperature message
Jumper 1 Output signal (V) Temperature °C Description
0.5 Alarm
1–10 10–100 Supplied tempera
ture
Tab.23 Output message
Jumper 2 Output signal (V) Heat output (%) Description
%
0 0–15 Boiler off
0.5 15–20 Alarm
2.0–10(1) 20–100 Supplied heat output
(1) Dependent on the minimum modulation depth (set speeds, standard 20%)
Fig.31 Switch jumper (2)
AD-0000055-01
1
2
%
2 2
Fig.32 Switch jumper (1)
AD-0000056-01
1
2
%
1 1
5 Installation
7684359 - v.11 - 13122021 29
29


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Quinta ACE 65 T-Control at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Quinta ACE 65 T-Control in the language / languages: English as an attachment in your email.

The manual is 4.19 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Quinta ACE 65 T-Control

Remeha Quinta ACE 65 T-Control Usermanual and installation guide - German - 116 pages

Remeha Quinta ACE 65 T-Control Usermanual and installation guide - Dutch - 80 pages

Remeha Quinta ACE 65 T-Control Usermanual and installation guide - French - 84 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info