Code Display text Description Solution
H.01.14 Max Tflow Flow temperature has exceeded the
maximum operating value
Flow temperature sensor above normal range:
Bad connection: check the wiring and connec
tors
No flow or insufficient flow:
Check the circulation (direction, pump,
valves)
Check the water pressure
Check the cleanliness of the heat exchanger
H.01.15 Max Tflue Gas Flue gas temperature has exceeded
the maximum operating value
Maximum flue gas temperature exceeded:
Check the flue gas outlet system
Check the heat exchanger to ensure that the
flue gas side is not clogged
Faulty sensor: replace the sensor
H.01.21 Dhw Temp GradLevel3 Maximum Dhw Temperature Gradi
ent Level3 Exceeded
The flow temperature has risen too fast:
Check the flow (direction, pump, valves)
Check that the pump is operating correctly
H.02.00 Reset In Progress Reset In Progress Reset procedure active:
No action
H.02.02 Wait Config Number Waiting For Configuration Number Configuration error or unknown configuration
number:
Reset CN1 and CN2
H.02.03 Conf Error Configuration Error Configuration error or unknown configuration
number:
Reset CN1 and CN2
H.02.04 Parameter Error Parameter Error Factory settings incorrect:
Parameters are not correct:
Restart the boiler
Reset CN1 and CN2
Replace the CU-GH PCB
H.02.05 CSU CU mismatch CSU does not match CU type Configuration error:
Reset CN1 and CN2
H.02.09 Partial block Partial blocking of the device recog
nized
Blocking input active or frost protection active:
External cause: remove external cause
Wrong parameter set: check the parameters
Bad connection: check the connection
H.02.10 Full Block Full blocking of the device recog
nized
Blocking input is active (without frost protection):
External cause: remove external cause
Wrong parameter set: check the parameters
Bad connection: check the connection
H.02.12 Release Signal Release Signal input of the Control
Unit from device external environ
ment
Waiting time release signal has elapsed:
External cause: remove external cause
Wrong parameter set: check the parameters
Bad connection: check the connection
H.02.31 AF needed Device requires Auto filling of the
water system due to low pressure
Refill the central heating system using the auto
matic (re)filling unit.
H.02.38 No water hardness No hardness of water -
H.02.70 HRU test error External heat recovery unit test
failed
Heat recovery unit non-return valve check failed:
Check the external heat recovery unit non-re
turn valve.
H.03.00 Parameter Error Safety parameters level 2, 3, 4 are
not correct or missing
Parameter error: security kernel
Restart the boiler
Replace the CU-GH
H.03.01 CU to GVC data error No valid data from CU to GVC re
ceived
Communication error with the CU-GH:
Restart the boiler
10 Troubleshooting
7684359 - v.11 - 13122021 59
59


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Quinta Ace 30 - T-Control at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Quinta Ace 30 - T-Control in the language / languages: English as an attachment in your email.

The manual is 4.19 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info