Quinta 45/65
28
End point (10 Volt): adjustable between +51°C and (( (+299)°C, factory default
)0 (100)°C.
This value sets the required flow temp at 10 Volt signal input (restricted by the max
flow set point).
NOTE: These settings are only applicable when boiler control operation parameter (A)
has the x value set to 4.
6.7 Read-out mode (X00)
To check boiler set points and values.
Using the m’-key, press repeatedly until !(flashing dot) appears in the ‘code’-display.
Then select the required code @, # or $ etc. using the ‘s’-key.
Table 10 Read-out mode user level
6.8 Fan speed mode (<00)
Using the m’ -key, press repeatedly until ‘code’-display shows alternate flashing half
digits.
The value in the t-display shows the actual fan speed using two alternate double
digits as table:
Table 11 Fan speed mode service level
Code Description
Read-out
(example)
! Actual flow temperature 80
@ Actual return temperature 70
# Actual DHW temperature (only with sensor) 58
$ Actual outdoor temperature (with Chronotherm sensor) 05
% n/a 3&
^ Flow temperature (set point) 80
& Actual heat demand status 1x = demand;
0x = no demand
* Calculated HTG cut-in temperature 67
( Actual flow temperature rise [0.1 °C/sec] 02
A n/a
Code Description Example 5250 r/m
, Fan speed 52 hundreds
> Fan speed 50 units14
28


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Quinta 45 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Quinta 45 in the language / languages: English as an attachment in your email.

The manual is 0,93 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Quinta 45

Remeha Quinta 45 Manual - Dutch - 2 pages

Remeha Quinta 45 User Manual - Dutch - 76 pages

Remeha Quinta 45 User Manual - Dutch - 76 pages

Remeha Quinta 45 User Manual - Dutch - 1 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info