Code Display text Description Solution
E.02.04 Parameter Error Parameter Error Configuration error:
Reset CN1 and CN2
See
The data plate for the CN1 and CN2
values.
E.02.13 Blocking Input Blocking Input of the Control Unit
from device external environment
Blocking input is active:
External cause: remove external cause
Wrong parameter set: check the parameters
E.02.15 Ext CSU Timeout External CSU Timeout CSU time out:
Bad connection: check the wiring and connec
tors
Faulty CSU: Replace CSU
E.02.17 GVC CommTimeout Gas Valve Control unit communica
tion has exceeded feedback time
Communication error with the security kernel:
Restart the boiler
Replace the CU-GH
E.02.35 Safety device lost Safety critical device has been dis
connected
Communication fault
Carry out an auto-detect
E.02.47 Failed Conn Funct Gr Failed Connecting Function Groups Function group not found:
Carry out an auto-detect
Restart the boiler
Replace the CU-GH
E.02.48 Funct Gr Conf Fault Function Group Configuration Fault SCB not found:
Carry out an auto-detect.
E.02.70 HRU test error External heat recovery unit test
failed
Heat recovery unit non-return valve check failed:
Check the external heat recovery unit non-re
turn valve.
E.04.00 Parameter error Safety parameters Level 5 are not
correct or missing
Replace the CU-GH.
E.04.01 TFlow Closed Flow temperature sensor is either
shorted or measuring a temperature
above range
Flow temperature sensor short circuited:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
E.04.02 TFlow Open Flow temperature sensor is either
removed or measuring a tempera
ture below range
Flow temperature sensor open:
Bad connection: check the wiring and connec
tors
Faulty sensor: replace the sensor
E.04.03 Max Flow temp Measured flow temperature above
savety limit
No flow or insufficient flow:
Check the circulation (direction, pump, valves)
Check the water pressure
Check the cleanliness of the heat exchanger
E.04.04 TFlue Closed Flue temperature sensor is either
shorted or measuring a temperature
above range
Flue gas temperature sensor short-circuited:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
E.04.05 TFlue Open Flue temperature sensor is either re
moved or measuring a temperature
below range
Flue gas temperature sensor open:
Bad connection: check the wiring and connec
tors
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Faulty sensor: replace the sensor
10 Troubleshooting
7734324 - v.06 - 01102021 75
75


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Gas 320 Ace at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Gas 320 Ace in the language / languages: English as an attachment in your email.

The manual is 6.49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Gas 320 Ace

Remeha Gas 320 Ace Usermanual and installation guide - German - 104 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info