Code Display text Description Solution
E.00.08 THeat Ex Open Heat exchanger temperature sensor
is either removed or measures a
temperature below range
Heat exchanger temperature sensor open:
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
E.00.09 THeat Ex Closed Heat exchanger temperature sensor
is either shorted or measures a tem
perature above range
Heat exchanger temperature sensor short-circuit
ed:
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
E.00.20 TFlue Gas Open Flue gas temperature sensor is ei
ther removed or measures a temper
ature below range
Open circuit in flue gas sensor:
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
E.00.21 TFlue Gas Closed Flue gas temperature sensor is ei
ther shorted or measures a tempera
ture above range
Flue gas sensor short-circuited:
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
E.00.40 WaterPressureOpen Water pressure sensor is either re
moved or measures a temperature
below range
Hydraulic pressure sensor open:
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
E.00.41 WaterPressureClosed Water pressure sensor is either
shorted or measures a temperature
above range
Hydraulic pressure sensor short-circuited:
Bad connection: check the wiring and connec
tors.
Incorrectly fitted sensor: check that the sensor
has been correctly fitted.
Faulty sensor: replace the sensor.
E.01.04 5x Flame Loss Error 5x Error of unintended Flame Loss
occurance
Flame loss occurs 5 times:
Vent the gas supply to remove air
Check that the gas valve is fully opened
Check the gas supply pressure
Check the operation and setting of the gas
valve unit
Check that the air supply inlet and flue gas out
let are not blocked
Check that there is no recirculation of flue
gases
E.01.12 Return Higher Flow Return tempearture has a higher
temperature value than the flow tem
perature
Flow and return reversed:
Bad connection: check the wiring and connec
tors
Water circulation in wrong direction: check the
circulation (direction, pump, valves)
Incorrectly fitted sensor: check that the sensor
has been correctly fitted
Malfunctioning sensor: check the Ohmic value
of the sensor
Faulty sensor: replace the sensor
10 Troubleshooting
74 7734324 - v.06 - 01102021
74


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Gas 320 Ace at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Gas 320 Ace in the language / languages: English as an attachment in your email.

The manual is 6.49 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Gas 320 Ace

Remeha Gas 320 Ace Usermanual and installation guide - German - 104 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info