Remeha Gas 3002
32
live and neutral inversion Switch off power and change connections.
switch off power, and change connections.
code not valid. The control unit does not recognize the boiler through the code connector.
check wiring. Check the wiring.
code not accepted. A wiring error has been made or a failure has occurred in the control unit.
please contact qualified personnel. Contact our service department.
flow sensor short circuit. Check the wiring of the respective temperature sensor.
return sensor short circuit. If wired correctly, replace the respective sensor and/or wiring.
heatexch. sensor short circuit.
flue sensor short circuit.
flow sensor open circuit.
return sensor open circuit.
heatexch. sensor open circuit.
flue gas sensor open circuit.
flow sensor overheat Too high temperature has been signalled.
return sensor overheat Check: - the water flow through the boiler/installation
heatexch. sensor overheat - the water level in the boiler
- the operating pressure (0.8 bar min.).
flue gas temperature too high Check: - the set maximum flue gas temperature (see par. 7.3.3, option no. 4)
Minimum setting: 15°C above maximum return water temperature
- the boiler setting
- the boiler for fouling
return temp. higher than heat exch. The return water temperature exceeds the first heat exchanger temperature.
temp. Check: - if the wiring of heat exchanger and return sensors have been inverted
- if the flow direction through the boiler is correct
return temp. higher than The return water temperature exceeds the flow water temperature.
flow temp. Check: - if the wiring of the flow and return sensors have been inverted
- if the flow direction through the boiler is correct
purge airpress. not reached During pre-ventilation the required min. air pressure differential across the boiler is not obtained.
Check: - the flue gas discharge, air supply and/or boiler for fouling
airpress. lost during purge - the diameter of the flue gas discharge/air supply pipes, using the tables of par. 5.5
- measurement tubes for fouling/humidity
insufficient airpress. during stage 1 The air pressure differential at low load is too low. It should be 50 Pa at least.
burning Check: - flue gas discharge, air supply and/or boiler for fouling
airpress. start not reached - fan, frequency regulator (see par. 10.9) and air pressure sensor
airpress. start lost - measurement tubes
insufficient airpress. during stage 2 The air pressure differential at high load is too low.
burning Check: - flue gas discharge, air supply and/or boiler for fouling
- fan, frequency regulator (see par. 10.9) and air pressure sensor
- measurement tubes
airpress. too high at stage 1 The air pressure differential is too high.
Check: - fan, frequency regulator (see par. 10.9) and air pressure sensor
airpress. detected when fan is off During standstill of the boiler too high a standstill draught is signalled (> 25 Pa).
Install a resistance in the flue gas discharge or air supply.
Check connections on air pressure differential switch (LDS).
Instructions
Failure message on LCD-display
32


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Gas 3002 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Gas 3002 in the language / languages: Dutch as an attachment in your email.

The manual is 1 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Gas 3002

Remeha Gas 3002 User Manual - German - 28 pages

Remeha Gas 3002 Manual - Dutch - 2 pages

Remeha Gas 3002 User Manual - Dutch - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info