11. Now select the option 'Fan on?' and confi rm with the
'
'-button. The fan will start now. Switch the fan to
maximum speed by selecting this option. Confi rm with
the ' '-button. Now press the ' '-button. Select the
option 'Service settings' and confi rm with the ' '-
button. Press the ' '-button. Select the option 'Pres-
sure settings'; confi rm with the ' '-button.
Set the maximum differential pressure at 900 Pa,
using the ' '-button. Confi rm with the ' '-button.
Now press several times the ' '-button until you reach
the menu where you can read out the air differential
pressure.
A differential pressure of min. 900 Pa has to be
reached. If not, check the dimensions of the fl ue gas
discharge system. Set the maximum differential pres-
sure in the service level back at the standard level of
750 Pa. Confi rm with the ' '-button. Set the minimum
differential pressure at 110 Pa for a minimum load
of 33% (minimum return water temperature then is
45°C) or at 240 Pa for minimum load of 50% (mini-
mum return water temperature is 35°C).
12. Check the opening pressure of the gas block.
Connect a pressure differential device to the measu-
ring points pG and pF (see fi g. 19 for 7 and 9 sections
and g. 20 for 11 to 19 sections).
Open the main gas cock (vent the gas line). Discon-
nect the ignition device from the ignition electrode.
Press several times the '
'-button, until you reach
the menu with the selecting option 'Service settings'.
Select this option and confi rm with the '
'-button.
Now select 'Boiler on?'; confi rm with the ' '-button.
The boiler now will make a start attempt without igni-
tion. As soon as the gas valve opens, the opening
pressure can be read out on the pressure differential
device. The ope ning pressure should be bet ween 1
and 3 mbar. When you read out a higher pressure,
turn the N-controller to the left. Repeat point 12
after resetting the boiler. When the openings pressure
lies between 1 and 3 mbar, a correct pre-setting is
assured. Connect the ignition device again to the igni-
tion electrode and reset the boiler. Select in the serv-
ice level again the option 'Service tests' and confi rm
with the ' '-button.
13. The cursor is now placed on option 'Boiler on?'.
Press the ' ' button. The control unit will now start
from neutral position. After an internal check and a
check of the differential air pressure, the fan will start.
As soon as the differential air pressure is suffi ciently
high, the pre-purge time is started. The fan now pre-
purges for 30 seconds at full load. Then the fan slows
to minimum load. The pre-ignition is activated and the
gas valve opened. If, at the end of the safety time,
there is a suffi cient signal from the pilot fl ame (the
ame is checked with a second ionisation probe) the
boiler will start operating at part load (mi ni mum load).
Gas multi-block
Gas distribution pipe
Fig. 19 Differential pressure measuring points (boiler with 7 and 9 sections)
blue
black
burner
black
blue
Side view
gas = PL+PG
air = PL+PF
29


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Gas 3002 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Gas 3002 in the language / languages: Dutch as an attachment in your email.

The manual is 1 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Gas 3002

Remeha Gas 3002 User Manual - German - 28 pages

Remeha Gas 3002 Manual - Dutch - 2 pages

Remeha Gas 3002 User Manual - Dutch - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info