10.5.2 Blocking inputs
The control system is equipped with two blocking inputs
which can switch off the boiler. These inputs can be
used, for example, in combination with the limit switches
of throtling valves, minimum gas pressure switches, etc.
Blocking input 1 is tted on terminals 29 and 30, whilst
blocking input 2 is fi tted on terminals 31 and 32.
The symbol for both inputs is:
If you wish to use either input, the wire bridge must rst
be removed. As long as the input is opened, the relevant
message will appear on the display until the contact is
made.
10.5.3 Locking input
The control system is equipped with one input which may
lock the boiler. These input can be used, for example, in
combination with the maximum gas pressure switch. The
locking input is fi tted on terminals 33 and 34.
The symbol for the input is:
If you wish to use the input, the wire bridge must rst
be removed. As long as the input is opened, the boiler
will be locked, and the relevant message will appear on
the display. Once the contact is closed, the boiler must
once again be released via the reset button.
10.5.4 Gas leak check
A gas leak check, to be supplied by Remeha, can be
connected to inputs 37 and 38. In this case, the control
must be adjusted for the presence of the gas leak check
at the service level (see para. 7.3.3, option 7).
The symbol for this input is:
B1. Through an analog signal
Select in the service level the option 'Input selection:
analog'. This analog signal (0-10V) should be connected
to the terminals 27 (-) and 28 (+) on the ter mi nal strip in
the boiler control panel and is indicated by the following
symbol:
The input resistance at the analog input is approx. 10 k
(see also electrical wiring diagram at para. 10.9). This
signal represents the start command and the required
output of the boiler according to g. 16.
The analog 0-10 V tension must be tension-free com-
pared to earth at both poles!
B2. Through the RS 232 bus.
Select in the service level the option 'Input selection:
computer'. Through a PC or BMS the start/stop com-
mand and the required ow temperature are now trans-
mitted to the boiler. Contact our technical department for
more information about RS 232 connection.
10.4.3 High/low control
It is also possible to control the boiler high/low.
The internal PI control cannot be used for high/low con-
trol. Switch off the internal control to select in the service
level the option 'Control selection: external' (see para.
7.3.3). The boiler now can operate on two volt free con-
tacts. The rst step should be connected to terminal 23
and 24 and is indicated by the following symbol:
The current through the contacts is approx. 6 mA. And
the second step to 25 and 26 is indicated by the fol-
lowing symbol:
The power for this input is supplied by the boiler at a level
of 24V DC. The current through the contacts is approx. 6
mA. The terminal strip is in the boiler control panel (see
the electrical wiring diagram at para. 10.9).
10.5 Connections
10.5.1 Other inputs
General:
All inputs (with the exception of the analog input) are
powered via the boiler with a voltage of 24 V DC.
The current is approx. 6 mA per input. No connection
whatsoever may be connected in any way with the
phase, zero or earth of the mains power circuit. All con-
nections must be made with potential-free contacts.
24


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Gas 3002 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Gas 3002 in the language / languages: Dutch as an attachment in your email.

The manual is 1 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Gas 3002

Remeha Gas 3002 User Manual - German - 28 pages

Remeha Gas 3002 Manual - Dutch - 2 pages

Remeha Gas 3002 User Manual - Dutch - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info