5.3 Hydraulic circuits with Low Loss Header
5.3.1 Single boiler installation
The boiler is weather compensated, taking into account a
minimum return water remperature of 35°C and the cir-
cuits are also weather compensated. The heating curve
of the boiler is then set approx. 5°C higher than the high-
est demanding circuit. Each circuit has its own pump.
The water fl ow is handled by a boiler pump sized for the
nominal ow rate of the boiler.
All gas appliances must, by law, be installed by com pe-
tent persons (e.g. Corgi) in accordance with the above
regulations. Failure to install appliances correctly could
lead to prosecution.
It is in your own interest and that of safety to ensure that
the law is complied with.
In addition to the above regulations, this appliance must
be installed in compliance with the current I.E.E. Regula-
tions for electrical installation, local building regulations,
the Building Standards (Scotland), Consolidation Regula-
tions, by laws of the local water undertaking and Health
and Safety Document No. 635 'The Electricity at Work
Regulations 1989'. It should also be in accordance with
the relevant recommendations in the current editions of
the following British Standards and Codes of Practice,
viz. BS 5440 Pt 1 and 2, BS 5449, BS 5546, BS 6798,
BS 6891 and BG.DM2.
Important:
The Remeha Gas 3002 is a certifi ed appliance and must
not be modifi ed or installed in any way contrary to these
"Installation and Servicing Instructions". Manufacturers
Instructions must NOT be taken in any way as overriding
statutory obligations.
5.5 Flue gas discharge and air supply
5.5.1 General
The Remeha Gas 3002 is available in either a conven-
tional room ventilated or a room sealed (Type B13, C33,
C53 or C63) construction. Specify at the time of ordering
if the boiler is required to be supplied for room sealed
operation. In that case, the boiler will be supplied with an
air supply connection and a clamping band.
This connection must be fi xed to the fan inlet (remove the
cover plate on the rear top casing).
- Conventional room ventilated operation:
The open boilers use ambient air as combustion air.
See para. 5.5.3 for a ue gas discharge table of the
Remeha Gas 3002 in room ventilated construction.
- Room sealed operation:
A sealed system is obtained by using an air supply
pipe. Because of this, the number of potential boiler
locations within the building is increased and less strin-
gent requirements are imposed on the discharge loca-
tion, since the air supply and the fl ue gas discharge are
in the same pressure area.
As open air is generally cleaner, the room sealed
option ensures max runtime before the heat exchanger
will need cleaning.
See para. 5.5.4 for a ue gas discharge/air supply
table of the Remeha Gas 3002 in room sealed
construction.
- Fan dilution system:
Between boiler and fan dilution system has to be an
open connection (draft diverter).
Fig. 05 L.L.H. with boiler pump with a single boiler
installation
5.3.2 Modular boiler installation
Example: 1 x condensing boiler + 1 x standard boiler
in modular arrangement with water-side shutdown of the
boiler which is out of operation, by means of a butterfl y
valve. The boilers are directly weather compensated, ta-
king into account a minimum return water temperature of
35°C for the standard boiler.
The heating curve of the boiler is then set approx. 5°C
higher than the highest demanding circuit.
For more information concerning hydraulic diagrams con-
tact our technical sales department.
Please note:
1) If the water resistance of boilers 1 and 2 is not the
same, the boiler with the less resistance should have
a regulating valve.
2) The condensing boiler is always the lead boiler.
5.4 Installation instructions
The following instructions must be adhered to when the
Remeha Gas 3002 is installed:
Gas Safety (Installation and Use) Regulations 1984 (as
amended).
Fig. 06 L.L.H. with boiler pump in a modular boiler
installation
100%
11


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Gas 3002 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Gas 3002 in the language / languages: Dutch as an attachment in your email.

The manual is 1 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Gas 3002

Remeha Gas 3002 User Manual - German - 28 pages

Remeha Gas 3002 Manual - Dutch - 2 pages

Remeha Gas 3002 User Manual - Dutch - 2 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info