Code Description Solution
E00.20 Flue gas temperature sensor is either removed or
measures a temperature below range
Open circuit in flue gas sensor:
Bad connection: check the wiring and connectors.
Incorrectly fitted sensor: check that the sensor has
been correctly fitted.
Faulty sensor: replace the sensor.
E00.21 Flue gas temperature sensor is either shorted or
measures a temperature above range
Flue gas sensor short-circuited:
Bad connection: check the wiring and connectors.
Incorrectly fitted sensor: check that the sensor has
been correctly fitted.
Faulty sensor: replace the sensor.
E00.40 Water pressure sensor is either removed or
measures a temperature below range
Hydraulic pressure sensor open:
Bad connection: check the wiring and connectors.
Incorrectly fitted sensor: check that the sensor has
been correctly fitted.
Faulty sensor: replace the sensor.
E00.41 Water pressure sensor is either shorted or measures
a temperature above range
Hydraulic pressure sensor short-circuited:
Bad connection: check the wiring and connectors.
Incorrectly fitted sensor: check that the sensor has
been correctly fitted.
Faulty sensor: replace the sensor.
E01.04 5x Error of unintended Flame Loss occurance Flame loss occurs 5 times:
Vent the gas supply to remove air
Check that the gas valve is fully opened
Check the gas supply pressure
Check the operation and setting of the gas valve
unit
Check that the air supply inlet and flue gas outlet
are not blocked
Check that there is no recirculation of flue gases
E01.12 Return tempearture has a higher temperature value
than the flow temperature
Flow and return reversed:
Bad connection: check the wiring and connectors
Water circulation in wrong direction: check the cir
culation (direction, pump, valves)
Incorrectly fitted sensor: check that the sensor has
been correctly fitted
Malfunctioning sensor: check the Ohmic value of
the sensor
Faulty sensor: replace the sensor
E02.04 Parameter Error Configuration error:
Reset CN1 and CN2
See
The data plate for the CN1 and CN2 val
ues.
E02.13 Blocking Input of the Control Unit from device
external environment
Blocking input is active:
External cause: remove external cause
Wrong parameter set: check the parameters
E02.15 External CSU Timeout CSU time out:
Bad connection: check the wiring and connectors
Faulty CSU: Replace CSU
E02.17 Gas Valve Control unit communication has exceeded
feedback time
Communication error with the security kernel:
Restart the boiler
Replace the CU-GH PCB
E02.35 Safety critical device has been disconnected Communication fault
Carry out an auto-detect
11 Troubleshooting
78 7665063 - v.05 - 18102018
78


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Remeha Gas 220 Ace at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Remeha Gas 220 Ace in the language / languages: English as an attachment in your email.

The manual is 9.39 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Remeha Gas 220 Ace

Remeha Gas 220 Ace Usermanual and installation guide - German - 88 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info