614013
13
Zoom out
Zoom in
Previous page
1/88
Next page
Product details | 13
6 720 816 739 (2015/05)MC 400
2.2.5 Output control
This control strategy is used when the heating system is controlled using
a building management system with a 0-10 V controller output.
Fig. 1 Linear relationship between the 0-10 V signal (U in volts) and
required performance P (in percent with reference to the
maximum system performance)
The connected heat sources are turned on and off according to the
required performance as per the module code as is the case with a serial
standard or serial optimized cascade.
2.2.6 Flow temperature control
This control strategy is used when the heating system is controlled using
a building management system with a 0-10 V controller output.
Fig. 2 Linear relationship between the 0-10 V signal (U in volts) and
required flow temperature
(in percent with reference to the
maximum flow temperature)
The connected heat sources are turned on and off according to the
required flow temperature as per the module code as is the case with a
serial standard or serial optimized cascade.
2.3 Setting the coding card
Fig. 3 Coding card with module status display, and a status display of
the connected heat sources or modules
2.4 Scope of delivery
Fig. 4, page 82:
[1] Module
[2] Bag with strain relief
[3] Installation instructions
2.5 Specifications
The design and operation of this product comply with
European Directives and the supplementary national
requirements. Its conformity is demonstrated by the CE
marking . You can ask for a copy of the declaration of conformity for this
product. For this purpose see the contact address on the back cover of
these instructions.
6 720 809 449-21.1O
P / %
U / V
1
10
100
1,5 10
6 720 809 449-22.1O
/ %
U / V
1
min
max
1,5 10
Coding Module function
0 Off (delivered condition)
1 Serial standard cascade
2 Serial optimized cascade ( Fig. 23, page 85)
3 Serial cascade with peak load coverage
4 Parallel cascade
5 No function
6 External 0-10 V performance control with serial standard cascade
7 External 0-10 V performance control with serial optimized cascade
( Fig. 24, page 86)
8 External 0-10 V flow temperature control with serial standard
cascade
9 External 0-10 V flow temperature control with serial optimized
cascade
10 The module is one of a maximum of 4 subordinate cascade modules.
The higher level cascade modules control the connected heat source
corresponding to the code noted on them ( Fig. 25, page 86).
Table 2 Coding and function
Specifications
Dimensions (W×H×D) 246×184×61mm (further
dimensions Fig. 5, page 82)
Maximum conductor cross-section
230 V terminal
Extra-low voltage terminal
•2.5mm
2
•1.5mm
2
Rated voltages
•BUS
Module mains voltage
User interface
Pumps and mixers
•15VDC
(reverse-polarity-protected)
230 V AC, 50 Hz
•15VDC
(reverse-polarity-protected)
230 V AC, 50 Hz
Fuse 230 V, 5 AT
BUS interface EMS 2 /EMS plus
Power consumption on – standby <1W
Max. output 1100 W
Table 3
13


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Nefit EMS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Nefit EMS in the language / languages: English, German, Dutch, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 4,41 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info