KICKSPACE
®
500, 600, 600-12V & 800
2.0 General Information
3.0 Heating System Design
l This MYSON KICKSPACE
®
fan convector is designed for
installation in the cavity beneath kitchen cupboards on the
vacant floor space, or other similar locations.
l No rear access shall be available to the unit after installation.
l The KICKSPACE
®
should only be used on closed circulation,
two pipe, pump assisted central heating systems.
l Before proceeding with the installation, the heating system
design must be considered and the unit correctly sized to
meet the heat loss requirements of the room.
l Flexible hoses with integral isolating valves are supplied to
allow easy installation and future access for maintenance.
l KICKSPACE
®
is supplied with integral controls including fan
speed selector and summer/winter switch.
l In heating mode a low limit thermostat prevents the fan from
operating if the heating system water temperature is below
32°C.
l In summer mode the fan can be operated to circulate a flow
of air without any heat supply.
l The KICKSPACE
®
600-12V is supplied with a separate 12V
transformer that enables the unit to be fitted in a bathroom.
Both the unit and the transformer must be positioned in
accordance with local and national regulations.
1.0 Safety Information (continued...)
Keep the appliance and its cord out
of reach of children aged less than 8
years.
Children of less than 3 years should
be kept away from the unit unless
continuously supervised.
Children aged from 3 years and less
than 8 years shall only switch on / off
the appliance provided that it has
been placed or installed in its
normal operating position and they
have been given supervision or
instruction concerning use of the
appliance in a safe way and
understand the hazards involved.
Children aged from 3 years and less
than 8 years shall not plug in, clean
the appliance or perform user
maintenance.
This fan convector must be fitted on a two pipe, pumped
circulation heating system.
For optimum fan convector heating performance the system
must be capable of providing sufficient hot water through the
heat exchanger. This means that:
1. The minimum pipe size from boiler to fan convector must be
at least 15mm. Microbore pipe MUST NOT be used.
2. Where the unit is fitted on to a system with other emitters a
separate circuit for the fan convector should be considered
to provide adequate water flow.
3. The system water must be above 32°C for fan to switch on.
Performance will depend on the water temperature at the coil
and the flow through the coil.
4. This unit is NOT suitable for one-pipe systems.
5. Optimum performance will require effective balancing of the
whole system.
6. This unit must not be used to replace a radiator in an existing
system unless an adequate flow of water can be guaranteed.
1.02.0
3.0
4.0 Selection and Sizing for Heating
l Heat output performance is given in the Technical Data
section of this manual.
l Since KICKSPACE
®
units are supplied with fan speed control
it is important to size the unit to match the calculated heat
loss requirements of the room with the unit operating at the
low fan speed.
l The higher fan speed can then be used for more rapid
heating from cold in extreme conditions.
4.0
KICKSPACE 500, 600, 600-12V & 800 INSTALLATION & MAINTENANCE MANUAL
01.01.2013 ISSUE 6
26690 Kickspace Manual for web_Layout 1 24/09/2013 10:07 Page 4
3


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Myson KICKSPACE 600-12V at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Myson KICKSPACE 600-12V in the language / languages: English as an attachment in your email.

The manual is 0,25 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Myson KICKSPACE 600-12V

Myson KICKSPACE 600-12V Usermanual and installation guide - Dutch - 6 pages

Myson KICKSPACE 600-12V Usermanual and installation guide - Dutch - 12 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info