6.6 ELECTRICAL CONNECTIONS
Checks to ensure electrical safety should be carried out by a qualified person
ALWAYS carry out the preliminary electrical system checks, i.e. earth continuity,
polarity, resistance to earth and short circuit using a suitable test meter.
6.7 FLUE GAS ANALYSIS
If the boiler is on a metered gas supply carry out a gas rate test at the gas meter. The
boiler needs to be in s
ervice mode which is achieved by turning the CH knob on the
front panel fully clockwise and the service LED will now be on. Turn the knob counter
clockwise and then fully clockwise again and the service LED will flash. The boiler is
now set in “high-rate” service mode. Turn on the hot water tap and carry out a gas rate
test at the gas meter. The gas consumption should be as below within a toleranc
e of
5%. If the reading is outside of this range then, with the use of a flue gas analyser,
refer to gas valve adjustment in chapter 7.
Gas Consumption
24CPM
30CPM
Unit
Natural Gas (max load)
2.38
2.92
m³/hour
Natural Gas (min load)
0.71
0.88
m³/hour
Propane (max load)
1.77
2.17
kg/hour
Propane (min load)
0.64
0.77
kg/hour
If no meter is available or the boiler is on bottled gas then, with the use of a flue
gas analyser, refer to gas valve adjustment in the chapter 7.
6.8 INITIAL OPERATION
Domestic hot water
To turn on the boiler follow the user instructions at the front of this manual.
Whenever a hot tap is opened the boiler automatically fires up to deliver hot water. The
temperature selector control should be se
t at maximum. If the ambient water
temperature is high (as in a hot climate) then the hot water temperature may be reduced
by using this knob.
Central heating
Set the timer/thermostat/programmer so that the boiler will fire in CH mode. Refer to
chapter 1 User Instructions to operate the CH circuit.
The central heating temperature control knob allows water temperature of between 30
and 80°C to be
selected. The boiler will remain on until:
The temperature selected on the thermostat/programmer is reached
The temperature selected on the boiler CH control knob is reached
The timer switches the boiler off.
28


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Morco 24CPM at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Morco 24CPM in the language / languages: English as an attachment in your email.

The manual is 7,72 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info