Next page
27
Control
Menu 2.2.4 [N] Min supply cooling
The set minimum level for the supply temperature to the
cooling system is shown here.
The calculated flow temperature never drops below the set
level irrespective of the outdoor temperature, cooling curve or
its offset.
HMA100 HMS140VA HMS140V
Setting range (°C) 7-25 7-25 7-25
*
2
Default value (°C) 10 18
*
1
18
*1 It is necessary to adjust the value for fancoil application.
Recommended value is 10.
*2 Do not set the value lower than 18°C. It may cause water
leak and damage your property or the product itself.
Menu 2.2.5 [N] Circ-pump speed cool
The speed of the circulation pump during cooling is selected
here.
Setting range: 1 – 100
Menu 2.2.6 [N] Return
Return to menu 2.2.0.
Menu 2.3 [U] Max supply temp.
The set maximum level for the supply temperature to the
heating system is shown here.
The calculated flow temperature never exceeds the set level
irrespective of the outdoor temperature, heating curve or offset
heating curve.
Setting range: 25 – 65 °C
Menu 2.4 [U] External adjustment
Connecting an external contact, for example, a room thermostat
(accessory) or a timer allows you to temporarily or periodically
raise or lower the room temperature. When the external contact
is closed, the heating curve offset or cooling curve offset is
changed by the number of steps shown here.
If room control is active there is a degree change to the set
room temperature.
Setting range: -10 – 10
Menu 2.5 [U] Supply/Return temp.
The current supply and return line temperatures are shown
here. Return temperature is shown in brackets.
Menu 2.6 [U] Degree minutes
Current value for number of degree-minutes. In addition, this
value can be changed to accelerate the start of heating production
or cooling.
Setting range: -32000 – 32000
Menu 2.7 [N] Return
Return to menu 2.0.
29


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Mitsubishi HMA100VM at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Mitsubishi HMA100VM in the language / languages: English as an attachment in your email.

The manual is 2,96 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info