MI 3100 s, MI 3100 SE EurotestEASI Measurements
45
5.5 Fault loop impedance and prospective fault current
Fault loop is a loop comprised by mains source, line wiring and PE path to the mains source.
The instrument measures the impedance of the loop and calculates the short circuit current.
The measurement is covered by requirements of the EN 61557-3 standard.
See chapter 4.2 Function selection for instructions
on key functionality.
Figure 5.23: Fault loop impedance
Test parameters for fault loop impedance measurement
Test Selection of fault loop impedance sub-function [Zloop, Zs rcd]
Fuse type Selection of fuse type [---, NV, gG, B, C, K, D]
Fuse I Rated current of selected fuse
Fuse T Maximum breaking time of selected fuse
Lim Minimum short circuit current for selected fuse
See Appendix A for reference fuse data.
Circuits for measurement of fault loop impedance
Figure 5.24: Connection of plug commander and 3-wire test lead
45


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI3100S at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI3100S in the language / languages: English as an attachment in your email.

The manual is 1.81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI3100S

Metrel MI3100S User Manual - German - 92 pages

Metrel MI3100S User Manual - Dutch - 25 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info