MI 3100 s, MI 3100 SE EurotestEASI Measurements
33
5.2 Insulation resistance
The insulation resistance measurement is performed in order to ensure safety against electric
shock through insulation. Typical applications are:
insulation resistance between conductors of installation,
insulation resistance of non-conductive rooms (walls and floors),
insulation resistance of ground cables and
resistance of semi-conductive (antistatic) floors.
See chapter 4.2 Function selection for instructions on
key functionality.
Figure 5.5: Insulation resistance
Test parameters for insulation resistance measurement
Uiso Nominal test voltage [50 V, 100 V, 250 V, 500 V, 1000 V]
Limit Minimum insulation resistance [OFF, 0.01 M ÷ 200 M]
Test circuits for insulation resistance
Figure 5.6: Connection of 3-wire test lead and tip commander
Insulation resistance measuring procedure
Select the R ISO function using the function selector switch.
Set the required test voltage.
Enable and set limit value (optional).
Disconnect tested installation from mains supply (and discharge insulation as required).
Connect test cable to the instrument and to the item to be tested (see Figure 5.6).
Press the TEST key to perform the measurement (double click for continuous
measurement and later press to stop the measurement).
After the measurement is finished wait until tested item is fully discharged.
Store the result by pressing the MEM key (MI 3100 SE only).
33


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI3100S at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI3100S in the language / languages: English as an attachment in your email.

The manual is 1.81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI3100S

Metrel MI3100S User Manual - German - 92 pages

Metrel MI3100S User Manual - Dutch - 25 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info