MI 3100 s, MI 3100 SE EurotestEASI Measurements
32
Voltage measurement procedure
Select the VOLTAGE TRMS function using the function selector switch.
Connect test cable to the instrument.
Connect test leads to the item to be tested (see Figure 5.2 and Figure 5.3).
Store voltage measurement result by pressing the MEM key (MI 3100 SE only).
Measurement runs immediately after selection of VOLTAGE TRMS function.
Figure 5.4: Examples of voltage measurement in three-phase system
Displayed results for single phase system:
Uln ............ voltage between phase and neutral conductors
Ulpe .......... voltage between phase and protective conductors
Unpe ........ voltage between neutral and protective conductors
f ................ frequency
Displayed results for three-phase system:
U12 ........... voltage between phases L1 and L2
U13 ........... voltage between phases L1 and L3
U23 ........... voltage between phases L2 and L3
1.2.3 ......... correct connection – CW rotation sequence
3.2.1 ......... invalid connection – CCW rotation sequence
f ................ frequency
32


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI3100S at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI3100S in the language / languages: English as an attachment in your email.

The manual is 1.81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI3100S

Metrel MI3100S User Manual - German - 92 pages

Metrel MI3100S User Manual - Dutch - 25 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info