MI 3121H Smartec 2,5 kV Insulation / Continuity Continuity
28
Test circuit for CONT resistance measurement
R
y
S
z
T
x
Figure 5.14: 2-wire test lead application
Continuous resistance measurement procedure
Select continuity function RLOW or CONT using the BACK / NEXT keys of
function selector.
Set sub-function CONT.
Enable and set the limit (optional).
Connect test lead to the instrument.
Compensate test leads resistance (if necessary, see section 5.2.3).
Disconnect from mains supply and discharge the object to be tested.
Connect test leads to the tested object (see Figure 5.14).
Press the TEST key to begin performing a continuous measurement.
Press the TEST key to stop measurement.
After the measurement is finished, store the result (optional).
Figure 5.15: Example of continuous resistance measurement
Displayed result:
Resistance.
Note:
Continuous buzzer sound indicates that measured resistance is less than 2 Ω.
28


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3121H SMARTEC 2.5 kV at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3121H SMARTEC 2.5 kV in the language / languages: English as an attachment in your email.

The manual is 1,21 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3121H SMARTEC 2.5 kV

Metrel MI 3121H SMARTEC 2.5 kV User Manual - German - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info