MI 3108 EurotestPV Instrument operation
32
Warning:
Customized settings will be lost when this option is used!
If the batteries are removed for more than 1 minute the custom made settings will
be lost.
The default setup is listed below:
Instrument setting
Default value
Language
English
Contrast
As defined and stored by adjustment procedure
Isc factor
1.00
RCD standards
EN 61008 / EN 61009
Commander
Enabled
Communication
RS232
Clamp settings
CLAMP 1
CLAMP 2
A1391, 40A
A1391, 40A
Solar settings
See chapter 4.4.10 Solar Settings
Test mode:
Function
Parameters / limit value
Sub-function
INSTALLATION:
EARTH RE
No limit
R ISO
No limit
Utest = 500 V
Low Ohm Resistance
R LOW
No limit
CONTINUITY*
No limit
Z - LINE
Fuse type: none selected
VOLTAGE DROP
ΔU: 4.0 %
ZREF: 0.00 Ω
Z - LOOP
Fuse type: none selected
Zs rcd
Fuse type: none selected
RCD
RCD t
Nominal differential current: IN=30 mA
RCD type: AC non-delayed
Test current starting polarity: (0)
Limit contact voltage: 50 V
Current multiplier: 1
POWER:
CURRENT
C1
HARMONICS
U
I
U
h:1
ENERGY
I: 40A, U: 260A
SOLAR:
32


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Metrel MI 3108 - Eurotest PV at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Metrel MI 3108 - Eurotest PV in the language / languages: English as an attachment in your email.

The manual is 3.81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Metrel MI 3108 - Eurotest PV

Metrel MI 3108 - Eurotest PV User Manual - German - 136 pages

Metrel MI 3108 - Eurotest PV User Manual - Dutch - 62 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info