Mass Systemswitch 16 kW (230V) User and Installation Manual
6.3.3 Menu level 3: Configuration
Value
Meaning
Factory
setting
Adjustable. range
General
Language
Language that is displayed on a monitoring device connected
to the MasterBus
English
English/ Nederlands/
Deutsch/ Français
Device
name
Name of this device. This name will be recognized by all
connected devices
Systemswitch
0-12 chars
Generator
Gen. U low
on
Lower acceptance voltage for pass through of AC power at the
generator input
205V
191-223V
Gen. U low
off
Lower rejection voltage for pass through of AC power at the
generator input
150V
124-177V
Gen. F low
on
Lower acceptance frequency for pass through of AC power at
the generator input
48Hz
41-60Hz
Gen. F low
off
Lower rejection frequency for pass through of AC power at the
generator input
43Hz
35-55Hz
Ignore gen
freq.
If set to On, the generator input ignores the frequency of AC
power at the generator input
Off
Off/On
Generator
Power
Maximum power of the AC-source that is connected to the
Generator input. In general, this is the nominal output power of
the generator set.
16kVA
0-16.0kVA
Names
Shore
name
Name of the AC input Shore
Shore
0-16 characters
Generator
name
Name of the AC input Generator
Generator
0-16 characters
Auto load
on inv.
LOI gen
load
The automatic load on inverter mode (see sections 3.6) will be
triggered when the generator load exceeds this percentage
(percentage of the Generator Power setting).
100%
0-100%
LOI gen
delay
Time delay for the automatic load on inverter mode (see
sections 3.6) caused by a generator overload. It prevents the
automatic load on inverter mode being activated due to a short-
time peakcurrent.
5s
0-30s
LOI
generator
To enable the automatic load on inverter mode triggered by the
generator load, this parameter must be set to “On”
Off
Off/On
LOI shore
load
The automatic load on inverter mode (see sections 3.6) will be
triggered when the shore load exceeds this percentage
(percentage of the Shore fuse setting; see section 6.3.1)
100%
0-100%
LOI shore
To enable the automatic load on inverter mode triggered by the
shore load, this parameter must be set to “On”
Off
Off/On
LOI runtime
When the automatic load on inverter mode is activated, it is
switched off again when the adjusted time has elapsed.
120min
5-540min
Events
Event x
source
Event-based command (see section 5.2)
Event by the Mass Systemswitch that should result in an action
by one of the other devices on the MasterBus network
(See List of events,
section 6.3.4)
Event x
target
Event-based command (see section 5.2)
Selection of device on the MasterBus network that should take
action due to an event. by the Mass Systemswitch
(See Device list on the
remote control panel)
Event x
command
Event-based command (see section 5.2)
Action to be taken by the selected device.
(See List of event
commands in the manual
of the selected device,)
Event x
data
Event-based command (see section 5.2)
Value of the action to be taken by the selected device.
(See List of event
commands in the manual
of the selected device,)
Art. nr
Serial
Shows the article number and the serial number of the Mass
Systemswitch
(read only)
18


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Mastervolt Mass Systemswitch 16 kW at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Mastervolt Mass Systemswitch 16 kW in the language / languages: English as an attachment in your email.

The manual is 1.28 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info