3.5 Positioning of the unit
In the continuation are illustrated some sequences of the
assembly:
1. Carry out the drilling on the ceiling and fix six M8
threaded rods as shown in the figure.
2. Position the unit on the six threaded rods (eight brac-
kets available).
3. Block the unit by locking the bolts.
3.7 Connection to the ducts
The ducts must be dimensioned in function of the system and of the air flow characteristics of the unit ventilators. A wrong calculation of the
ducts may cause loss of power or the possible activation of devices fitted on the unit.
Severe bending, several bending and diameter reductions of the ducts should be avoided to minimize the pressure loss.
In order to prevent the formation of condense and to reduce the noise level it is advised to use insulated ducts.
If rigid ducts are used, to avoid the transmission of possible vibrations of the machine in the atmosphere, it is advised to interpose an antivi-
brating joint between the air outlets and yhe ducts. The electrical continuity between duct and machine must however be guaranteed through
a earth cable.
The distance between indoor inlet port and indoor intake port should be as far as possible
In order to prevent the penetrations of rains, the ducts connecting the unit with the outside should be protected by grilles.
Moreover the ducts should be a little tilted
IMPORTANT: IT IS PROHIBITED TO START UP THE UNIT, IF THE FANS OUTLETS ARE NOT CANALIZED OR PROTECT WITH AN ACCI-
DENT-PREVENTION NET AS PER UNI 9219 AND SUCCESSIVE NORMS.
Exhaust air
duct
Indoor Intake
duct
Room intake
opening
Supply air duct
Threaded rods (min 6)
Outside
intake air
Outside intake duct
Brackets
Inside supply
opening
3.6 Drain tray connection
Close to supply air duct connection, a drain tray outlet
(1/4” hose pipe) shall be connected for discharge of con-
densed water during cooling mode.
It is strongly suggested to install a water trap close to
the unit in order to avoid odors coming inside and to get
a slope on discharge pipeline.
pag. 12
12


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Kaysun KRE-500DX1 at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Kaysun KRE-500DX1 in the language / languages: English as an attachment in your email.

The manual is 2.81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info