A main switch or other means of disconnection, having a contact separation in all poles, must be incorporated in the
fixed wiring in accordance with relevant local laws and regulations. Switch off the power supply before making any
connections. Use only copper wires. Never squeeze bundled cables and make sure they do not come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the terminal connections. All field wiring and
components must be installed by a licensed electrician and must comply with relevant local laws and regulations.
The field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions
given below.
Be sure to use a dedicated power supply. Never use a power supply shared by another appliance.
Be sure to establish a ground. Do not ground the unit to a utility pipe, surge protector, or telephone ground. Incomplete
grounding may cause electrical shock.
Be sure to install a ground fault circuit interrupter (30 mA). Failure to do so may cause electrical shock.
Be sure to install the required fuses or circuit breakers.
This unit is equipped with an inverter. Installing a phase advancing capacitor not only will reduce the power factor
improvement effect, but also may cause abnormal heating of the capacitor due to high-frequency waves. Never install a
phase advancing capacitor as it could lead to an accident.
Fix cables so that cables do not make contact with the pipes (especially on the high pressure side).
Secure the electrical wiring with cable ties as shown in figure so that it does not come in contact with the piping, particularly
on the high-pressure side.
Make sure no external pressure is applied to the terminal connectors.
When installing the ground fault circuit interrupter make sure that it is compatible with the inverter (resistant to high
frequency electrical noise) to avoid unnecessary opening of the ground fault circuit interrupter.
NOTE
The ground fault circuit interrupter must be a high- speed type breaker of 30 mA (<0.1 s).
7.1 Precautions on electrical wiring work
7 FIELD WIRING
WARNING
Equipment must be grounded.
All high-voltage external load, if it is metal or a grounded port, must be grounded.
All external load current is needed less than 0.2A, if the single load current is greater than 0.2A, the load must be controlled
through AC contactor.
7.2 Precautions on wiring of power supply
Use a round crimp-style terminal for connection to the power supply terminal board. In case it cannot be used due to
unavoidable reasons, be sure to observe the following instructions.
Do not connect different gauge wires to the same power supply terminal. (Loose connections may cause overheating.)
When connecting wires of the same gauge, connect them according to the figure below.
-
-
18
NOTE
Maximum length of communication wirings is 50m.
Power cords and communication wiring must be laid out separately, they can not be placed in the same conduit.
Otherwise, it may lead to electromagnetic interference. Power cords and communication wirings should not come in
contact with the refrigerant pipe so as to prevent the high temperature pipe from damaging the wires.
Communication wirings must use shielded lines.Including indoor unit to outdoor unit PQE line ,indoor unit to controller
ABXYE line.
21


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Kaysun KHPI-BI-16VR2XL at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Kaysun KHPI-BI-16VR2XL in the language / languages: English as an attachment in your email.

The manual is 38.52 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Kaysun KHPI-BI-16VR2XL

Kaysun KHPI-BI-16VR2XL User Manual - German - 44 pages

Kaysun KHPI-BI-16VR2XL User Manual - Dutch - 44 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info