7 - AERAULIC CONNECTIONS
7.1 AERAULIC DESIGN CRITERIA
If the duct outlets for the outdoor air inlet and exhaust are
outside of coverage, must end with a 90 ° bend downward, to
prevent entry of water from the air inlet.
To perform the ductings:
 Connect the ductings fixing them to the connections with
the special hookings to the circular flanges.
 The duct weight should not lie on the connection flanges.
 Put antivibration joints between ducts and units.
 The connection to the flanges and among the different
duct sections must guarantee the air seal, avoiding air
dispersions in supply and return that penalize the overall
efficiency of the installation.
 Limit the pressure drops by optimizing the path, the type
and the number of curves and branches.
 Use curves of large radius.
 For unit air outlet with duct, when unit operating,
condensate will be generated aroud outside of duct.
 Thermically insulate the supply ducts to avoid heat losses
and condensate.
7.2 AIR DUCT CONNECTION
The dimensioning and the correct execution of the aeraulic
connections are critical to ensure the unit operating and an
appropriate level of quietness in the served area.
Pressure loss in the duct will reduce the air flow, which can
cause a reduction in efficiency of the unit.
The maximum static pressure should be within 25Pa
7.3 DIMENSION CONNECTIONS
Avoid recirculation of exhaust/return air
Use elbows with a 90° downward bend
Minimum exhaust distance (M) / return distance (R)
Exhaust / return grille (Provided by the customer)
External air return
 positioned in an area with a low concentration of impuri-
ties (dust, odours, exhaust fumes, etc.).
Exhaust outlet
 away from terraces, balconies, property boundary lines;
 avoid windward zones
Unit 190
Unit 300
Grille Grille
Grille
Grille
Unit 300
Unit 190
Unit 190 Unit 300
R - External air return
M - Air supply
Unit 190 Unit 300
22


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Kaysun COMPAK KHPA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Kaysun COMPAK KHPA in the language / languages: English as an attachment in your email.

The manual is 14.06 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info