Switch off the power supply before opening the switch box service panel and making any changes to the DIP switch
settings.
Operate the switches with an insulated stick (such as a closed ball-point pen) to avoid electrostaric damage to the
components.
WARNING
During initial start-up and when water temperature is low, it is important that the water is heated gradually. Failure to do so may
result in concrete floors cracking due to rapid temperature change. Please contact the responsible cast concrete building
contractor for further details.
To do so, the lowest water flow set temperature can be decreased to a value between 25°C and 35°C by adjusting the FOR
SERVICEMAN. Refer to "FOR SERVICEMAN/special function/preheating for floor" .
DANGER
Switch off the power supply before making any connections.
After the installation of the unit, check the following before switching on the circuit breaker:
Field wiringMake sure that the field wiring between the local supply panel and unit and valves (when applicable),
unit and room thermostat (when applicable), unit and domestic hot water tank, and unit and backup heater kit have
been connected according to the instructions described in the chapter 9.6 Field wiring, according to the wiring
diagrams and to local laws and regulations.
Fuses, circuit breakers, or protection devices Check that the fuses or the locally installed protection devices are of
the size and type specified in the chapter 14 Technical specifications. Make sure that no fuses or protection devices
have been bypassed.
Backup heater circuit breakerDo not forget to turn on the backup heater circuit breaker in the switchbox (it
depends on the backup heater type). Refer to the wiring diagram.
Booster heater circuit breakerDo not forget to turn on the booster heater circuit breaker (applies only to units with
optional domestic hot water tank installed).
Ground wiringMake sure that the ground wires have been connected properly and that the ground terminals are
tightened.
Internal wiringVisually check the switch box for loose connections or damaged electrical components.
MountingCheck that the unit is properly mounted, to avoid abnormal noises and vibrations when starting up the
unit.
Damaged equipmentCheck the inside of the unit for damaged components or squeezed pipes.
Refrigerant leakCheck the inside of the unit for refrigerant leakage. If there is a refrigerant leak, call your local
dealer.
Power supply voltageCheck the power supply voltage on the local supply panel. The voltage must correspond to
the voltage on the identification label of the unit.
Air purge valveMake sure the air purge valve is open (at least 2 turns).
Shut-off valvesMake sure that the shut-off valves are fully open.
Checks before initial start-up.
10.3 Initial start-up at low outdoor ambient temperature
10.4 Pre-operation checks
1 2 3 4 1 2 3 4
S1 S2
ONOFF
1 2 3 4
S4
ON=1 OFF=0
1Reserved
2
DIP
switch
2
0/0=Without IBH and
AHS
1/0=With IBH
0/1=With
AHS for heat mode
1/1=With
AHS for heat mode
and DHW mode
3/4
1
3/4
ON=1 OFF=0
DIP
switch
S1 S2
Reserved
Factory
defaluts
Start pumpo
after 24 hours
will be invalid
Factory
defaluts
Without TBH With TBH
0/0=variable speed pump,
Max head: 8.5m
0/1=constant speed pump
1/0=variable speed pump,
Max head: 10.5m
1/1=variable speed pump,
Max head: 9.0m
DI P
switch
S4
1
2
3/4
Factory
defaluts
ON=1 OFF=0
Keep the
current
address
Reserved
Reserved Reserved Reserved Reserved
Refer to
eletrically
controlled
wiring
diagram
Refer to
eletrically
controlled
wiring
diagram
Refer to
eletrically
controlled
wiring
diagram
Start pumpo
after 24 hours
will be invalid
Master unit:clear
address of all slave
units
Slave unit:clear its
own address
47


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Kaysun Aquantia PRO Monobloc - KHP-MO at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Kaysun Aquantia PRO Monobloc - KHP-MO in the language / languages: English as an attachment in your email.

The manual is 27.62 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Kaysun Aquantia PRO Monobloc - KHP-MO

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - German - 88 pages

Kaysun Aquantia PRO Monobloc - KHP-MO User Manual - Dutch - 88 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info