USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Page 13 of 13 EZ-CHEM Rev. B
Troubleshooting guide
As most malfunctions are related to a poor water balance, we advise you to check it before handling the product (see
chemical water balance).
Alarm text Possible causes Recommendation Action
“Flow” ashing Insufcient ow or no ow
Check the operation of the ow switch; if the contact is
closed, "FLOW" remains steady, otherwise it ashes.
The fault automatically
disappears once the
problem is resolved
Check that the lter pump is working correctly
Check the operating periods on the programming clock
Ensure that all the valves are open
Ensure that the water ows freely in the pipes
OFA Alr (pH)
Setting time too low Increase the pH OFA alarm time (20 minutes to
240 minutes)
Press CAL Enter to
remove the fault
Or set the pH OFA alarm
to OFF.
Acid container empty Replace the acid container
Rigid injection pipe blocked or pinched Inspect the acid injection pipe, replace if necessary
Peristaltic pump problem
Check pump operation, press the (+) button to force it to
operate, replace the pump if faulty
Inspect the membrane, replace if necessary
Difculty reading the pH or unstable pH Check the water balance and recalibrate the pH probe
OFA STOP (pH) pH level not reached after 3 cycle times See recommendation for pH OFA Alarm Press CAL Enter to
remove the fault
OFA Alr (Rx)
Setting time too low Increase the Redox OFA alarm time (20 minutes to
240 minutes) Press CAL Enter to
remove the fault
Or set the Rx OFA alarm
to OFF.
Chlorine container empty Replace the liquid chlorine container
Rigid injection pipe blocked or pinched Inspect the chlorine injection pipe, replace if necessary
Peristaltic pump problem
Check pump operation, press the (-) button to force it to
operate, replace the pump if faulty
Inspect the membrane, replace if necessary
Difculty to read Redox Check the water balance and recalibrate the ORP probe
OFA STOP (Rx) Redox level not reached after 3 cycle
times See Rx OFA Alr recommendation Press CAL Enter to
remove the fault
Parameter error System error Restore the default settings N/A
Electronic problem, replace the device
Error 7 pH
pH probe calibration problem Repeat the calibration
The fault automatically
disappears once the
problem is resolved
pH probe faulty Check the pH probe connection with the BNC connector
on the housing, inspect the probe and the cable
pH buffer solution out of date Obtain a new solution
Error 4 pH
pH probe calibration problem Repeat the calibration
pH probe faulty Check the pH probe connection with the BNC connector
on the housing, inspect the probe and the cable
pH buffer solution out of date Obtain a new solution
Error 465 mV
Rx probe calibration problem Repeat the calibration
Rx probe faulty
Check the connection of the Rx probe with the BNC
connector on the housing, inspect the probe and the
cable
Rx buffer solution out of date Obtain a new solution
27


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Hayward EZ-Chem at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Hayward EZ-Chem in the language / languages: English, German, French, Italian, Spanish as an attachment in your email.

The manual is 59.76 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info