13
4.154.14 4.16
Metering and control in ppm of
the free chlorine of the water.
Optional Free Chlorine control 4.14 Calibration of the Free Chlorine probe:
Recommended every month during usage season.
4.15 Calibration with buffer (photometer DPD1): Follow
the instructions in 6 steps that appear in the display.
4.16 Step 1 of 6 - Calibrate Cl at 0 ppm (offset): Close
the water flow through the probe and wait until the
reading is less than 0,10 ppm. Wait between 5 to 60
min. Press OK when the reading is close to 0.
4.184.17 4.19 4.17 Step 3 of 6 - Calibrate Cl: Open the water flow
until achieving 80-100 liters/hour. Wait until obtaining
a stable reading of ppm. Wait between 5 to 20 min.
Press OK when the reading is stable.
4.18 Step 5 of 6 - Establish the real ppm values
with the plus/minus keys according to your analysis
result of DPD1 (free chlorine).
4.19 Step 6 of 6 - If this screen is not shown repeat
the calibration process.
Free Chlorine probe
4.3 MEASURES / Free Chlorine calibration
4.20 4.21 4.21 Manual calibration: Open de water flow and
set the flowmeter (rotameter) at the right level of
flow (80-100l/h). Wait some minutes until the current
level is stable. With the plus/minus keys, insert
manually the water chlorine level (use a manual
DPD1 test kit). Press OK when the DPD1 value is
correct on display (target measurement).
5. FILTRATION / Manual mode
5.1 5.2 5.1 Filtration:
Configuration control of the filter pump. To set, select
Filtration and confirm by pressing OK . The mode
selection is done in Mode line with the plus/minus keys.
5.2 Manual:
Manually turns ON/OFF the filtration process. No timing
or additional functions. The State line indicates whether
the filtration pump is ON.
See section Filter Cleaning below.
110-230 V max. 3.15 A DRY CONTACT
FILTER PUMP
Filtration control
4.4 MEASURES / Conductivity calibration
4.23 4.244.22
Metering and control of
the conductivity of the
water in Msiemens.
Optional Conductivity probe 4.22 Calibration of the Conductivity probe:
Recommended every month during usage season.
4.23 Calibration with buffer (buffer solution 1413 µS/
12880 µS/ neutro): Follow the instructions in 7 steps
that appear in the display (screen 4.24 corresponds
to step 1).
4.25 4.26 4.25 Manual calibration: Allows to adjust the probes
at 1 point (without buffers) – only recommended to
adjust small deviation in the readings.
4.26 Without removing the probe from the water,
use the plus/minus keys to adjust the reading so it
matches with your reference value (photometer or
other measurement).
4.5 MEASURES / Temperature calibration
4.28 Temperature calibration: To set difference
between the measured value of the probe and the
actual temperature, use the plus/minus and up/down
keys. Set to the actual temperature of the probe and
press OK.
4.27 4.28
Temperature probe
necessary to activate
the filtration modes:
heating, intelligent,
smart.
Optional Temperature
Temperature
probe
Setup and connection of a Variable Speed
Pump, see section 13 - Variable Speed Pump
1
1
2
2
3
3
4
red black
3 4
4
5
6
7
8
Chlorine probe detector
FL2 (rotameter)
3
5
6
black
brown
blue
1
2
3
red
yellow
black
Conductivity probe
1 yellow
2 transparent
1 2 3 4 5 678910 11 12 13 14
7 & 8
14
12 11
A1 A2
LN
1
2
1 2 3
13


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Hayward AquaRite UV LS at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Hayward AquaRite UV LS in the language / languages: English, German, Dutch, French, Italian, Portuguese, Spanish as an attachment in your email.

The manual is 6.81 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info