Installation & Programming Guide — 33
Default Configuration.
The contents of the communicator’s configuration can be defaulted to a known state by
defaulting the panel’s NVM — see Defaulting Instructions).
Programmable Restore Code Reporting.
When any channel goes into alarm the communicator will always initiate an alarm report
call.
Normally, the transition from alarm to restore is ignored by the communicator. However,
any channel(s) programmed for restore reporting will report the restore condition.
Programmable Open/Close Code Reporting.
Not all of the 8 channels necessarily represent alarm data. Any of the 8 channels may be
programmed to report a modified code. The alarm receiver will interpret ‘open’ instead of
‘alarm’ and ‘close’ instead of ‘restore’ for these channels.
Selection of Open/Close will override selection of Alarm and Restore Reporting. Close
codes are always reported in this instance.
The eight channels can be programmed in any combination of Alarm Only, Alarm/Restore
and Open/Close code reporting.
Multiple Message Reporting.
The possibility of missing rapidly changing events are greatly reduced by the inclusion of
an event history buffer in the communicator. Any alarm event sent to the communicator
will be stored in a queue for sending to the central station, and messages sent to the
central station are taken off the queue in a first come, first processed basis. As messages
are transmitted to the central station, more events can be received, processed and
transmitted within the current telephone call.
Primary/Secondary Reporting.
The communicator will make 3 connect attempts to call the receiver at the Primary
Telephone number in the configuration store. If all these attempts fail, and if a telephone
number has been entered in the Secondary Number Store, it will make the same number
of attempts to call the receiver at the Secondary Telephone number. If all these attempts
fail, then the communications failure status is sent to the panel. As soon as a receiver is
contacted, and all the outstanding alarms sent, then the sequence is halted. If a message
is successfully transmitted then Comms OK is reported to the panel. The panel event log
will record “Primary OK” or “Secondary OK”. The remote receiver can be programmed to
be Ademco Fast Format, Contact_ID, Guardall format or a hand held pager.
Dual Reporting
The communicator will make 3 connect attempts to call the receiver at the Primary
Telephone number. As soon as an attempt is successful, or all attempts fail, then it will
make the same number of attempts to call the receiver at the Dual Telephone number, if a
Dual number has been defined. When both receivers have been contacted, and all
outstanding alarms sent to both, then the sequence is halted. The panel Event Log will
record “Primary OK” or “Dual OK” or both.
The remote receiver can be programmed to be Ademco Fast Format, Point_ID, Guardall
format or a hand held pager.
33


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Guardall WINDSOR SERIES 300i at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Guardall WINDSOR SERIES 300i in the language / languages: English as an attachment in your email.

The manual is 0,3 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info