52 GMC-I Messtechnik GmbH
14.1 Voltage Drop Measurement (at Z
LN
) – U Function
Significance and Display of U (per DIN VDE 100, part 600)
Voltage drop from the intersection of the distribution network and
the consumer system to the point of connection of an electrical
power consumer (electrical outlet or device connector terminals)
should not exceed 4% of nominal line voltage.
Calculating voltage drop (without offset):
U = Z
L-N
• nominal current of the fuse
Calculating voltage drop (with offset):
U = (Z
L-N
- Z
OFFSET
) • nominal current of the fuse
U in % = 100 • U / U
L-N
See also section 9 regarding measurement procedure and connection.
Connection and Test Set-Up
Set Parameters
Note: When the nominal current I
N
is changed with existing
U
OFFSET,
the offset value is automatically adjusted.
Setting Limit Values
TAB Limit value per German technical connection conditions
for connection to low-voltage mains between the distribu-
tion network and the measuring device
DIN Limit value per DIN 18015-1: U < 3% between the mea-
suring device and the consuming device
VDE Limit value per DIN VDE 0100-520: U < 4% between the
distribution network and the consuming device (adjustable
up to 10% in this case)
NL Limit value per NIV: U < 5%
Measurement without OFFSET
Proceed as follows:
Switch OFFSET from ON to OFF.
Determine OFFSET (as %)
Proceed as follows:
Switch OFFSET from OFF to ON. “UOFFSET = 0.00%” is dis-
played.
Connect the test probe to the point of common coupling
(measuring device / meter).
Start measurement of offset with I
N
.
An intermittent acoustic signal sounds first,
which is then accompanied by a blinking
warning to prevent an offset value which has
already been saved from being unintentionally
deleted.
Start the offset measurement by
pressing the release key again or
abort measurement by pressing the
key t ON/START (here = ESC).
U
OFFSET x.xx % is indicated, where x.xx may take a value
between 0.00 and 99.9 %.
An error message appears in a pop-up window in the event that
Z > 10 .
Start Measurement with OFFSET
1
2
Nominal current of the fuse:
Polarity selection: Lx-N
Diameter: 1.5 to 70 sq. mm
Cable types: NY..., H03... - H07...
Number of wires: 2 ... 10-strand
Tripping characteristics: B, L
2 to 160 A
Limit value
U % > limit value
U
L
R
L
U
Red
2
52


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt PROFITEST MXTRA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt PROFITEST MXTRA in the language / languages: English as an attachment in your email.

The manual is 2,28 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Gossen Metrawatt PROFITEST MXTRA

Gossen Metrawatt PROFITEST MXTRA User Manual - Dutch - 92 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info