Settings for Short-circuit current Calculation – Parameter I
K
Short-circuit current I
K
is used to test shutdown by means of an
overcurrent protective device. In order for an overcurrent protec-
tive device to be tripped on time, short-circuit current I
K
must be
greater than tripping current Ia (see table 6 in section 21.1). The
variants which can be selected with the “Limits” key have the fol-
lowing meanings:
I
K
: Ia The measured value displayed for I
K
is used without
any correction to calculate Z
L-PE
.
I
K
: Ia+% The measured value displayed for Z
L-PE
is corrected
by an amount equal to the test instrument’s measuring
uncertainty in order to calculate I
K
.
I
K
: 2/3 Z In order to calculate I
K
, the measured value displayed
for Z
L-PE
is corrected by an amount corresponding to
all possible deviations (these are defined in detail by
VDE 0100, part 600, as Z
s(m)
2/3 x U
0
/Ia).
I
K
: 3/4 Z Z
s(m)
3/4 x U
0
/Ia
I
K
Short-circuit current calculated by the instrument (at nominal
voltage)
Z Fault loop impedance
Ia Tripping current (see data sheet for circuit breakers / fuses)
%
Test instrument inherent error
Special case I
k
> I
kmax
If the value for the short-
circuit current is beyond
the measured values
defined in
PROFITEST MASTER, it is
indicated by > IK-max“.
In this case, it will be
necessary to evaluate
the measuring result
manually.
Start Measurement
Display of U
L-N
(U
N
/ f
N
)
If the measured voltage value lies within a range of 10% of the
respective nominal line voltage of 120 V, 230 V or 400 V, the
respectively corresponding nominal line voltage is displayed. In
the case of measured values outside of the 10% tolerance, the
actual measured value is displayed.
Displaying the Fuse Table
After measurement has been performed, allowable fuse types can
be displayed by pressing the HELP key.
The table shows maximum allowable nominal current dependent
upon fuse type and breaking requirements.
Key: Ia = breaking current, I
K
= short-circuit current,
I
N
= nominal current, t
A
= tripping time
Semiautomatic measurement
See also section 5.8 regarding the
AUTO parameter. L-PE relationships are
not possible here. The neutral L-N rela-
tionship is not offered during automatic
sequencing to the right of the auto en-
try!
Polarity selection
Limit value:
I
K
< limit value
U
L
R
L
I
K
29


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt PROFITEST MXTRA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt PROFITEST MXTRA in the language / languages: English as an attachment in your email.

The manual is 2,28 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Gossen Metrawatt PROFITEST MXTRA

Gossen Metrawatt PROFITEST MXTRA User Manual - Dutch - 92 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info