7.4 Testing Residual Current Circuit Breakers in TN-S Systems
Connection
RCCBs can only be used in TN-S systems. An RCCB would not
work in a TN-C system because PE is directly connected to the
neutral conductor in the outlet (it does not bypass the RCCB).
This means that residual current would be returned via the RCCB
and would not generate any differential current, which is required
in order to trip the RCCB.
As a rule, the display for contact voltage is also 0.1 V, because
the nominal residual current of 30 mA together with minimal loop
resistance results in a very small voltage value:
7.5 Testing of RCD Protection in IT Systems with High Cable
Capacitance (e.g. in Norway)
The desired system type (TN/TT oder IT) can be selected for RCD
test type U
IN
(I
N
, t
a
), and for earthing measurement (R
E
).
A probe is absolutely essential for measurement in IT systems,
because contact voltage U
IN
which occurs in these systems
cannot otherwise be measured.
After selecting the IT system setting, connection with probe is
selected automatically.
Set the Parameter – Select System Type
Start Measurement
UINR
E
IN 130mA 30mV 0
·
03V,== ==
System
type:
25


Need help? Post your question in this forum.

Forumrules


Report abuse

Libble takes abuse of its services very seriously. We're committed to dealing with such abuse according to the laws in your country of residence. When you submit a report, we'll investigate it and take the appropriate action. We'll get back to you only if we require additional details or have more information to share.

Product:

For example, Anti-Semitic content, racist content, or material that could result in a violent physical act.

For example, a credit card number, a personal identification number, or an unlisted home address. Note that email addresses and full names are not considered private information.

Forumrules

To achieve meaningful questions, we apply the following rules:

Register

Register getting emails for Gossen Metrawatt PROFITEST MXTRA at:


You will receive an email to register for one or both of the options.


Get your user manual by e-mail

Enter your email address to receive the manual of Gossen Metrawatt PROFITEST MXTRA in the language / languages: English as an attachment in your email.

The manual is 2,28 mb in size.

 

You will receive the manual in your email within minutes. If you have not received an email, then probably have entered the wrong email address or your mailbox is too full. In addition, it may be that your ISP may have a maximum size for emails to receive.

Others manual(s) of Gossen Metrawatt PROFITEST MXTRA

Gossen Metrawatt PROFITEST MXTRA User Manual - Dutch - 92 pages


The manual is sent by email. Check your email

If you have not received an email with the manual within fifteen minutes, it may be that you have a entered a wrong email address or that your ISP has set a maximum size to receive email that is smaller than the size of the manual.

The email address you have provided is not correct.

Please check the email address and correct it.

Your question is posted on this page

Would you like to receive an email when new answers and questions are posted? Please enter your email address.



Info